Back to Tools DirectoryIndustrial Motor Starting Guide

Synchronised Generator & Heavy Pump Sizer

Deploying large dewatering pumps and municipal stormwater boosters powered by 1 MW+ portable generators requires strict transient analysis. The sudden inrush of a heavy pump can collapse alternator terminal voltage, tripping AC contactors across the entire distribution busbar. This tool calculates busbar voltage dip, ISO 8528-5 compliance classes, and starter torque margins under BS 7671 Section 551 and ISO 8528-5.

Contactor Retention & ISO 8528-5 Rule: Standard AC contactor operating coils release when control voltage drops below 65% to 80% nominal potential. Generator transient busbar dip must never exceed 20.0% (≥ 320 V retained) without dedicated DC latching supplies or uninterruptible power.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Generator & Heavy Pump Ratings
Heavy Pump Motor Rating (kW)200 kW
Shaft output rating of the largest pump motor starting against the generator.
2. Starting Method & Alternator Subtransient Reactance
Alternator Subtransient Reactance (Xd") 0.13 p.u.
Internal subtransient reactance governs instantaneous initial voltage drop (0.08 to 0.25 p.u.).
Pump FLC: 370 AStarting Surge: 898 kVA
BASIS: ISO 8528-5 & BS 7671 §551ISO 8528-5 Class G4 (≤ 10% Dip)
Transient Busbar Voltage Dip (ΔV)
8.5%
Retained Potential: 366 V during motor acceleration
Inrush Ratio0.72x
Starting Current1295 A
ISO 8528 ClassClass G4
0% (Ideal)8.5% Busbar Dip20% Contactor Danger
Class G4 (≤10%)Class G3 (≤15%)Class G2 (≤20%)Dropout Risk (>20%)
Starter Output Torque & Switchgear Telemetry
Starting Torque Available: 20.9% · Feeder Breaker: 1600 A ACB · Cable: 50m
Starting Torque & Busbar Integrity Assessment:
Soft Starter Torque Trap: Clamping current to 3.5x FLC reduces starting torque to 20.9% of nominal rating. Verify that the static fluid head and pump impeller breakaway torque do not exceed 20.9%, otherwise the pump will stall and burn thyristors before reaching full speed.
Site Conditions & Secondary Feeder ParametersStandard (400V · Xd'' 0.13 · 50m Feeder · 1600A ACB · 7.0x LRC)
Show Full Mathematical Derivation (ISO 8528-5 & BS 7671 §551)
ISO 8528-5 / BS 7671 §551
Step-by-step engineering workingTransparent first-principles maths
Step 1 · Pump Full-Load Current & Inrush Surge

Motor Full-Load Current & Starting Surge kVA

I_flc = (P_motor × 1000) / (√3 × V × pf × η)
(200 kW × 1000) / (√3 × 400 × 0.85 × 0.92) → 370 A (Surge: 898 kVA)
BS EN 60034-1 · Three-Phase Motor Starting Inrush
Step 2 · Inrush Ratio & Alternator Reactance

Per-Unit Alternator Equivalent Impedance

k_inrush = S_start / S_gen · X_motor_pu = 1 / k_inrush
898 kVA / 1250 kVA = 0.72x → Xd'' = 0.13 p.u.
ISO 8528-5:2018 Clause 13.2 · Subtransient Voltage Division
Step 3 · Transient Busbar Voltage Dip

Instantaneous Alternator Voltage Division

ΔV_sub% = [Xd'' / (Xd'' + X_motor_pu)] × 100%
[0.13 / (0.13 + 1.39)] × 100% → 8.5% (ΔV) → 366 V Retained
ISO 8528-5 Class G4 (≤ 10% Dip) · BS 7671 Reg 551.4.1
Step 4 · Starter Available Torque & Contactor Margin

Depressed Voltage Torque Reduction & Coil Retention

T_available% = (V_retained / V_nom)² × (I_start / I_lrc)² × 100%
(366 / 400)² × (3.5 / 7.0)² × 100% → 20.9% Available Torque
BS EN 60947-4-1 Clause 8.2 · Contactor Holding Voltage Floor
Worked Example & Engineering Rationale: 1.25 MVA Quarry Dewatering

Design Scenario: A 1,250 kVA diesel generator (Xd" = 0.13) powers a 200 kW high-lift quarry dewatering pump.

  • Motor Full-Load Current: 200 kW at 0.85 pf and 92% efficiency draws 370 A FLC at 400 V.
  • Soft Starter Inrush: Clamping starting current to 3.5x FLC draws 1,295 A (898 kVA surge).
  • Transient Voltage Dip: 898 kVA / 1250 kVA = 0.72x inrush ratio. Alternator voltage division results in (0.13 / (0.13 + 1.39)) × 100 = 8.5% dip.
  • Retained Potential: 400 V drops to 366 V during motor acceleration (ISO 8528-5 Class G4 Pass).
  • Soft Starter Torque Trap: Starting torque is reduced by voltage squared and current squared to only 20.9% nominal torque. If pump static fluid column breakaway exceeds 21%, motor stalls.
Formula & factors cross-checked against ISO 8528-5 / BS 7671 §551. Free of black-box approximations.
Excitation Support & Earth Fault Safety:Without Permanent Magnet Generator (PMG) or auxiliary winding excitation, a sustained generator short-circuit fault collapses the magnetic field within 300 ms, dropping fault current below full-load current (FLC). Thermal-magnetic circuit breakers will fail to trip on sustained downstream faults. PMG excitation and independent earth bonding under BS 7430 and BS 7671 Table 54.7 are mandatory on all industrial generator installations.

Standards reference: ISO 8528-5:2018 (Transient performance), BS 7671:2018+A3:2024 Section 551 & Table 54.7, BS 7430:2011+A1:2015, BS EN 60947-4-1:2019.