Synchronised Generator & Heavy Pump Sizer
Deploying large dewatering pumps and municipal stormwater boosters powered by 1 MW+ portable generators requires strict transient analysis. The sudden inrush of a heavy pump can collapse alternator terminal voltage, tripping AC contactors across the entire distribution busbar. This tool calculates busbar voltage dip, ISO 8528-5 compliance classes, and starter torque margins under BS 7671 Section 551 and ISO 8528-5.
Contactor Retention & ISO 8528-5 Rule: Standard AC contactor operating coils release when control voltage drops below 65% to 80% nominal potential. Generator transient busbar dip must never exceed 20.0% (≥ 320 V retained) without dedicated DC latching supplies or uninterruptible power.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
Excitation Support & Earth Fault Safety:Without Permanent Magnet Generator (PMG) or auxiliary winding excitation, a sustained generator short-circuit fault collapses the magnetic field within 300 ms, dropping fault current below full-load current (FLC). Thermal-magnetic circuit breakers will fail to trip on sustained downstream faults. PMG excitation and independent earth bonding under BS 7430 and BS 7671 Table 54.7 are mandatory on all industrial generator installations.
Standards reference: ISO 8528-5:2018 (Transient performance), BS 7671:2018+A3:2024 Section 551 & Table 54.7, BS 7430:2011+A1:2015, BS EN 60947-4-1:2019.