Van Mode: On-Site Quick Reference

High-contrast, tactile lookup suite designed for one-handed operation on mobile screens on site. Includes instant 80% Max Zs limits, standard cable ampacity, and BPG 4 EICR defect classifications per BS 7671:2018+A4:2026.

1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Field Reference Mode
2. Protective Device Parameters
BS 7671 Table 41.2 to 41.4 disconnection tables.
Select rated current matching protective device on site.
GS38 Site Basis: Null test leads before measuring loop impedance; verify cold ambient 80% rule against tabulated values.

Field Test Telemetry

Max Permitted Measured Zs (80% Cold Rule)
1.10 Ω
Operating Limit: 1.37 ΩDisconnection: 0.4s
Standard CitationTable 41.3BS 7671:2018+A4
Temperature Multiplier0.80 ×ambient test adjustment
Conductor Basis70°C PVCthermoplastic rating
Nominal Rating32 Aprotective device In
PASSTabulated limit 1.37 Ω. On-site measured limit is 1.10 Ω (80% cold rule applied).
Supply Earthing System & Temperature AdjustmentsStandard: TN-C-S · Cold 80% Rule · 30mA RCD
Affects statutory disconnection and electrode requirements.
Checks if supply impedance alone exceeds circuit limit.
On-Site Guide Appendix B temperature correction.

Glass-Box AM2 Derivation: Fault Loop Impedance Calculation Pad

Step-by-step mathematical trace derived per BS 7671:2018+A4:2026 Chapter 41 and On-Site Guide Appendix B.

Step 1: Stated Test Limits
Zs(test) ≤ 0.8 × Zs(tab)
Zs(test) ≤ 1.10 Ω (Operating: 1.37 Ω)
Step 2: Regulation Formula
Zs(tab) ≤ (U0 × Cmin) / Ia
(230V × 0.95) / Ia = 1.37 Ω
Step 3: Cold Circuit Adjustment
0.80 Temperature Multiplier
0.80 × 1.37 Ω = 1.10 Ω
Step 4: Statutory Notice
EAWR 1989 Reg 14
Verify with calibrated GS38 test instrument