Back to Tools DirectoryCable Sizing Guide

BS 7671 Voltage Drop Calculation Instrument

Calibrated digital instrument for BS 7671:2018+A4:2026 Regulation 525.1. Evaluates single-phase and three-phase voltage drop from first principles with Appendix 4 tables, cumulative submain budgeting, and ring final topology.

Plant-Room Ready: This calculator caches to your phone and works 100% offline with zero mobile signal. Add to your home screen for instant on-site access.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Supply & System Configuration
2. Conductor Specification & Run
Tabulated Value:18 mV/A/mTable 4D5

Calculation Summary

Standard Basis: BS 7671:2018+A4:2026 · Reg 525.1 · Appendix 4Topology: Radial (Full L)
Calculated Circuit Voltage DropTwin & Earth · 2.5 mm²
10.80 V(4.70%)
Why not adjacent conductor size?Evaluating conductor boundary criteria...
Voltage Drop Headroom (Reg 525.1)
10.80 V (4.70%)PASS · ≤ 5.0%
0 V3% (6.9V)5% (11.5V)Limit
Headroom Margin:+0.70 V (+0.30% margin)
Statutory Permitted Allowance:11.50 V (5.00%)
Upstream Submain Deduction:0.00% (Direct from origin)
Maximum Permissible Route Length:31.9 m
Maximum Permissible Current:21.3 A
Conforms to BS 7671:2018+A4:2026 Appendix 4 deemed-to-satisfy benchmarks.
Site Conditions & AdjustmentsStandard (70°C max · Public Supply · 0% Upstream)
Upstream Submain Cumulative Drop (%) · Reg 525.1Deducted: 0.00%
% drop consumed between origin and sub-distribution board
Cumulative intake budget per BS 7671 Reg 525.1. Calculated in percentage points to maintain accuracy across 400V 3-phase submains and 230V 1-phase final circuits. Assumes submain drop evaluated at diversified submain current.
Supply Network OriginTable 4Ab Basis
Show Full Mathematical Derivation (AM2 Working Standard)
BS 7671:2018+A4:2026
Step-by-step engineering workingTransparent first-principles maths
Step 1 · Circuit Parameters & Unit Value

Tabulated Millivolt Drop Lookup

mV/A/m from BS 7671 Appendix 4 Tables
Tabulated: 18.00 mV/A/m (Table 4D5 · Twin & Earth 2.5 mm²)
  • Tabulated Unit: 18.00 mV/(A·m)
  • Design Current (Ib): 20.00 A
  • Route Length (L): 30.0 m (Effective Length: 30.0 m)
  • Circuit Topology: Radial Distribution (Leff = L)
Step 2 · Temperature Correction Factor (Ct)

Operating Conductor Temperature (App 4 §6.1)

Ct = [230 + tp - (Ca²Cg² - (Ib²/It²))(tp - 30)] / [230 + tp]
Ct = 1.000 (Conservative worst-case tabulated operating temperature)
BS 7671 Appendix 4 Section 6.1 · Clamped to ≤ 1.000
Step 3 · Calculated Voltage Drop (Vd)

Ohmic Drop Across Conductor Loop

Vd = (mV/A/m × Ct × Ib × Leff) / 1000
Vd = (18.00 × 1.000 × 20.00 × 30.0) / 1000 = 10.80 V
For 3-phase circuits, tabulated mV/A/m already incorporates line-to-line √3 factor
Step 4 · Percentage Drop & Upstream Submain Budget

Cumulative Statutory Verification (Reg 525.1)

% Vd = (Vd / Vnominal) × 100 ≤ (% Total Limit - % Upstream)
% Vd = (10.80 / 230) × 100 = 4.70% ≤ (5.00% - 0.00% = 5.00%) · COMPLIANT
  • Nominal Voltage: 230 V
  • Calculated Percentage: 4.70% (10.80 V)
  • Upstream Submain Drop: 0.00%
  • Final Circuit Remaining Budget: 5.00% (11.50 V)
  • Headroom Margin: +0.70 V (+0.30%)
Step 5 · Permissible Boundary Limits

Maximum Route Run Length & Current Inverses

Lmax = (Vlimit × 1000) / (mV/A/m × Ct × Ib)
Lmax = (11.50 × 1000) / (18.00 × 1.000 × 20.00) = 31.9 m · Ib,max = 21.3 A
First-principles statutory inverse limits
Statutory Compliance Note:Worked evaluation to BS 7671:2018+A4:2026 Regulation 525.1. Table 4Ab figures represent deemed-to-satisfy statutory benchmarks. To be verified by a skilled electrical person before final sign-off (EAWR 1989 Reg 4).
Formula & factors cross-checked against BS 7671:2018+A4:2026. Free of black-box approximations.

Frequently Asked Questions

What are the statutory voltage drop limits under BS 7671?

Under BS 7671:2018+A4:2026 Appendix 4 (Section 6.4) and Table 4Ab, for low-voltage installations supplied directly from a public distributor network, maximum voltage drop between the installation origin and equipment terminals is 3% for lighting circuits (6.9 V at 230 V / 12.0 V at 400 V) and 5% for other uses such as heating and power sockets (11.5 V at 230 V / 20.0 V at 400 V). If supplied from a private substation or generator, limits increase to 6% and 8% respectively.

Why do three-phase calculations omit the √3 multiplier when using Table 4D4B / 4E4B?

In BS 7671 Appendix 4, tabulated mV/A/m values in three-phase columns are already line-to-line values pre-multiplied by √3. When calculating three-phase voltage drop using VD = (mV/A/m × Ib × L) / 1000, entering the balanced line current Ib and route length L gives the exact line-to-line drop directly without applying an additional √3 multiplier.

How does upstream submain voltage drop affect final circuit allowances?

The 3% lighting and 5% power limits represent the total cumulative budget from the origin of the installation (DNO cut-out) to the final point of utilisation. If a distribution submain has already consumed 1.5% of the supply voltage, the final sub-circuit must not exceed the remaining 3.5% allowance. This calculation is conducted in dimensionless percentage points to maintain mathematical consistency across 400V 3-phase submains and 230V 1-phase final circuits.

How does conductor operating temperature affect mV/A/m voltage drop?

Standard tabulated mV/A/m values in BS 7671 assume conductors operate at their maximum permissible temperature (70°C for thermoplastic PVC, 90°C for thermosetting XLPE). When design current Ib is significantly below cable tabulated capacity It, conductors run cooler and have lower electrical resistance, producing less voltage drop. Appendix 4 Section 6.1 provides the temperature correction factor Ct for precise assessments.