BS 7671 Voltage Drop Calculation Instrument
Calibrated digital instrument for BS 7671:2018+A4:2026 Regulation 525.1. Evaluates single-phase and three-phase voltage drop from first principles with Appendix 4 tables, cumulative submain budgeting, and ring final topology.
Frequently Asked Questions
What are the statutory voltage drop limits under BS 7671?
Under BS 7671:2018+A4:2026 Appendix 4 (Section 6.4) and Table 4Ab, for low-voltage installations supplied directly from a public distributor network, maximum voltage drop between the installation origin and equipment terminals is 3% for lighting circuits (6.9 V at 230 V / 12.0 V at 400 V) and 5% for other uses such as heating and power sockets (11.5 V at 230 V / 20.0 V at 400 V). If supplied from a private substation or generator, limits increase to 6% and 8% respectively.
Why do three-phase calculations omit the √3 multiplier when using Table 4D4B / 4E4B?
In BS 7671 Appendix 4, tabulated mV/A/m values in three-phase columns are already line-to-line values pre-multiplied by √3. When calculating three-phase voltage drop using VD = (mV/A/m × Ib × L) / 1000, entering the balanced line current Ib and route length L gives the exact line-to-line drop directly without applying an additional √3 multiplier.
How does upstream submain voltage drop affect final circuit allowances?
The 3% lighting and 5% power limits represent the total cumulative budget from the origin of the installation (DNO cut-out) to the final point of utilisation. If a distribution submain has already consumed 1.5% of the supply voltage, the final sub-circuit must not exceed the remaining 3.5% allowance. This calculation is conducted in dimensionless percentage points to maintain mathematical consistency across 400V 3-phase submains and 230V 1-phase final circuits.
How does conductor operating temperature affect mV/A/m voltage drop?
Standard tabulated mV/A/m values in BS 7671 assume conductors operate at their maximum permissible temperature (70°C for thermoplastic PVC, 90°C for thermosetting XLPE). When design current Ib is significantly below cable tabulated capacity It, conductors run cooler and have lower electrical resistance, producing less voltage drop. Appendix 4 Section 6.1 provides the temperature correction factor Ct for precise assessments.