Back to Tools Directory

3-Phase Power & Current Converter

Convert between electrical real power (kW), apparent demand (kVA), reactive magnetising load (kVAr), and line current (A). Includes automated capacitor bank sizing for power factor correction per BS EN 60034-1 and BS 7671 Chapter 55.

1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Supply Configuration & Real Power
7.5 kW
Real working power turned into heat, light, or shaft torque.
2. Power Factor & Compensation Target
0.85
1.0 for resistive heating; typically 0.80 to 0.88 for induction motors.
0.95
0.95 avoids UK DNO reactive power penalty charges.

AC Line & Phasor Readout

Symmetrical Line Current (RMS)
12.7 A
Apparent: 8.82 kVAReactive: 4.65 kVAr
Capacitor Bank Req2.18 kVArto achieve 0.95 PF
Current Reduction1.34 A (10.5%)feeder relief
Mechanical Horsepower10.06 hp1 hp = 0.7457 kW
Active Watts7,500 Welectrical input
Power Factor Vector Efficiency0.85 (85%)
0.50 Poor0.85 Typical0.95 DNO Ideal1.00 Unity
Balanced three-phase symmetrical load distribution calculated per BS EN 60034-1.
Supply Voltage Calibration & Motor Efficiency ParametersStandard: 400V 3Ø · 90% Motor Eff · 50 Hz
Standard UK: 230V 1-phase or 400V 3-phase.
Calculates actual mechanical shaft power output.
Affects capacitor reactance (Xc = 1 / 2πfC).

Glass-Box AM2 Derivation: First-Principles AC Phasor Pad

Step-by-step mathematical trace derived per AC polyphase phasor relationships, BS EN 60034-1, and BS 7671.

Step 1: Apparent Power (kVA)
S = P / pf
7.50 kW / 0.85 = 8.82 kVA
Step 2: Reactive Power (kVAr)
Q = √(S² - P²)
√(8.82² - 7.50²) = 4.65 kVAr
Step 3: Line Current Equation
I_L = P / (√3 × V_L × pf)
7500 / (1.732 × 400 × 0.85) = 12.74 A
Step 4: Capacitor Bank Sizing
Q_c = P × (tan φ1 - tan φ2)
7.5 kW × (0.620 - 0.329) = 2.18 kVAr