VFD Energy Savings & Payback Calculator

Slowing a centrifugal pump or fan delivers dramatic energy reductions because hydraulic power follows the cube of rotational speed: P₂ = P₁ × (N₂ / N₁)³. Dropping speed by just 20% slashes required power by nearly half. This tool calculates net annual electricity savings, capital payback periods, and carbon abatement in accordance with BS EN 61800-9-2 and ISO 50001.

1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Machine Rating & Operating Speed
15.0 kW
Absorbed electrical power at full speed (not just motor nameplate rating).
80%
Typical modulated flow demand under VFD automation.
6,000 hrs
8,760 hours equates to continuous 24/7 annual operation.
2. System Mechanics & Electricity Tariff
Static head does not reduce with speed. Overlooking static lift is the primary cause of missed energy targets.
28.0 p
Blended day/night electricity tariff from utility supply invoice.

VFD Payback & Energy Telemetry

Net Annual Financial Savings
£10,339/yr
Payback: 4.1 monthsPower Saved: 6.16 kW (41.0%)
New Running Demand8.84 kWincludes 3.0% drive loss
Annual Energy Saved36,936 kWhper 6,000 running hours
Power Reduction Efficiency41.0% Saved
0% (Direct On-Line)30% Typical60%+ High Affinity
Annual Carbon Abatement:7.65 tonnes CO&sub2;e/yr
Engineering Assessment:At 80% speed, a mixed system delivers a 41.0% power drop. Throttling via valves burns nearly full power against artificial friction; speed control eliminates this waste.
Capital Cost, Inverter Losses & Grid EmissionsStandard (£3,500 outlay · 3.0% drive loss)
Purchase, installation, harmonic chokes, and commissioning. Set to 0 to omit payback.
Typically 2% to 4% of drive throughput dissipated as cabinet heat per BS EN 61800-9-2.
UK DESNZ standard grid electricity emission factor (0.207 kg CO2e/kWh).

Glass-Box AM2 Derivation: First-Principles Energy Calculation Pad

Step-by-step mathematical trace derived per hydraulic affinity equations and BS EN 61800-9-2 drive system loss models.

Step 1: Hydraulic Affinity Power
P2 = P1 × (N2 / N1)^2.5
15.0 kW × (80% / 100)^2.5 = 8.59 kW
Step 2: Inverter Thermal Demand
P_elec = P_shaft × (1 + Losses)
8.59 kW × (1 + 3.0%) = 8.84 kW
Step 3: Annual Energy Difference
ΔE = (P_base - P_elec) × Hours
(15.0 - 8.84) × 6,000 = 36,936 kWh/yr
Step 4: Simple Financial Payback
36,936 kWh × 28.0p = £10,339/yr
£3,500 / £10,339 = 0.34 yrs (4.1 mos)