BS EN 60529:1992+A2:2013EAWR 1989 Reg 6

1. Ingress Protection (IP Code) Reference Deck

Pick an enclosure rating for adverse, wet, or dusty environments. An IP rating defines sealing effectiveness against solid foreign bodies and moisture under BS EN 60529. Verify statutory minimums under BS 7671 and the Electricity at Work Regulations 1989.

Bench Mentor Note: Statutory Law vs Consensus Standards

Regulation 6 of the Electricity at Work Regulations 1989 is statutory criminal law. It mandates that any electrical equipment exposed to weather, wet, dirty, or corrosive conditions must be constructed or protected to prevent danger.

BS 7671 (IET Wiring Regulations) and BS EN 60529 are non-statutory consensus standards. Conformity with these standards is deemed to satisfy the statutory safety duties of EAWR Regulation 6, but the standards themselves carry no direct criminal force.

Single-page A4 workshop & van noticeboard specification
Interactive IP Code DecoderSelect both digits to decode test specs, site applications, and non-cumulative warnings
IP55Dust Protected
Solid Ingress:Dust protected: ingress of dust is not entirely prevented, but does not enter in sufficient quantity to interfere with safe equipment operation.
Water Ingress:Protected against low-pressure water jets from all directions (12.5 litres/min at 30 kPa from 3 metres).
Typical Site Use:Industrial workshops, commercial EV chargers, and washdown bays.
Table 1: BS EN 60529 First Numeral (Solid Foreign Objects & Ingress Limits) • Verified 2026-10-31
DigitObject SizeHazardous Contact AccessTest Method & Acceptance
0NoneNo protection against contactNo test applied
1>= 50 mmBack of hand (IP1X / IPXXA)50 mm rigid sphere probe with 50 N force
2>= 12.5 mmFinger safe (IP2X / IPXXB)12.5 mm articulated test finger probe with 30 N force
3>= 2.5 mmTool protected (IP3X / IPXXC)2.5 mm test rod with 3 N force
4>= 1.0 mmWire safe (IP4X / IPXXD)1.0 mm rigid steel wire probe with 1 N force
5Dust protectedComplete contact preventionTalcum powder circulation under depression for 8 hours (limited ingress)
6Dust tightComplete contact preventionTalcum powder circulation under depression for 8 hours (zero ingress)
XUnspecifiedUnspecifiedNo test declared
Table 2: BS EN 60529 Second Numeral (Water Moisture & Cumulative Limits) • Verified 2026-10-31
DigitProtection LevelTest ParametersCumulative Status
0No ProtectionNo test appliedCumulative
1Vertically Dripping WaterDripping box 1 mm/min for 10 minCumulative
2Dripping Water Tilted 15 DegreesDripping box 3 mm/min for 2.5 min per 4 fixed tilt positionsCumulative
3Spraying Water (Rainproof)Oscillating tube or spray nozzle up to 60 degrees from vertical at 10 l/min for 10 minCumulative
4Splashing Water (Splashproof)Oscillating tube 360 degrees or spray nozzle with shield removed at 10 l/min for 10 minCumulative
5Water Jets6.3 mm nozzle delivering 12.5 l/min at 30 kPa core pressure from 2.5 to 3 m for 3 minCumulative
6Powerful Water Jets12.5 mm nozzle delivering 100 l/min at 100 kPa core pressure from 2.5 to 3 m for 3 minCumulative
7Temporary ImmersionSubmersion in water 0.15 m to 1.0 m depth for 30 minutesNon-cumulative (Jets not implied)
8Continuous SubmersionContinuous submersion under manufacturer specified pressure or depthNon-cumulative (Jets not implied)
9High-Pressure High-Temperature Water JetsFan and point nozzles delivering 14 to 16 l/min at 80 degrees C and 8 to 10 MPa (80 to 100 bar) at 0, 30, 60, 90 degreesNon-cumulative (Jets not implied)
XNot DeclaredNo test declaredCumulative
Table 3: UK Statutory & BS 7671 Mandatory Minimum Enclosure Sealing • Verified 2026-10-31
Installation Location / ApparatusMin IP RatingRegulation / ClauseLegal StatusOperational Notes
Enclosure top horizontal surfacesIP4X or IPXXDBS 7671 Reg 416.2.2● StandardNo entry of 1.0 mm wire probe. Mandatory for readily accessible top surfaces of distribution boards and consumer units.
Enclosure accessible vertical surfacesIP2X or IPXXBBS 7671 Reg 416.2.1● StandardNo finger contact with hazardous live parts (jointed 80 mm test probe, 12 mm diameter).
Outdoor EV charge pointsIP44 minimumBS 7671 Reg 722.512.2BS EN 60529 Clause 6● StandardDust protected against foreign bodies > 1.0 mm and splashing water. Higher ratings such as IP54 or IP65 are common manufacturer options but IP44 is the statutory minimum standard.
Underground joint boxes and cable pitsIP68BS 7671 Reg 522.3BS EN 60529 Clause 6● StandardPresence of water external influence AD. Continuous submersion under head of water. Resin or gel filled enclosure.
Bathroom Zone 0 (interior of bath or shower basin)IPX7BS 7671 Reg 701.512.2● StandardProtected against temporary immersion to 1 m depth. SELV not exceeding 12 V AC rms or 30 V ripple-free DC only.
Bathroom Zone 1 and Zone 2 (general locations)IPX4BS 7671 Reg 701.512.2● StandardSplashproof from any direction. 30 mA RCD protection mandatory on all circuits supplying the location.
Bathroom Zone 1 and Zone 2 (cleaning jets used)IPX5BS 7671 Reg 701.512.2● StandardRequired where water jets are used for cleaning, such as communal showers, sports facilities, and commercial washrooms.
External domestic socket outletsIP66 closed / IP56 in-useBS 7671 Reg 512.2● StandardExternal influences AD4 (water splashes or jets) and AE3 (small foreign bodies). Enclosure must maintain seal with standard 13 A plug inserted.
Adverse and wet environments (statutory baseline)Suitable construction and sealingEAWR 1989 Reg 6◆ StatuteCriminal statutory duty. Electrical equipment exposed to weather, natural hazards, wet, dirty, or corrosive conditions must be constructed or protected to prevent danger.

IPX9K vs IPX9 (BS EN 60529)Engineering Demarcation (ISO 20653)

IPX9K originates from road vehicle standard ISO 20653 (originally DIN 40050-9) for high-pressure washdown of automotive equipment. BS EN 60529 defines IPX9 for industrial enclosures with slightly different nozzle distances and pressure limits. The two standards are distinct and not interchangeable in statutory specifications.

ISO 20653 Table 7BS EN 60529 Clause 14.2.9
BS 7671:2018+A4:2026 Section 701SI 1989 No. 635 (as amended)

2. Bathroom & Shower Zones Spatial Reference

Locations containing a bath or shower present increased shock risk due to reduced skin resistance in wet contact. Section 701 prescribes rigorous zone boundaries, equipment restrictions, and protective measures.

Bench Mentor Note: On-Site Decision Making

Right, bathrooms. Measure every socket position horizontally from the Zone 1 boundary, not from the bath edge or the door. Under Reg 701.512.3, standard socket-outlets require at least 2.5 m separation from Zone 1. Every circuit serving the room needs 30 mA RCD protection, so test it, do not assume it. Before you skip supplementary bonding under Reg 701.415.2, prove all three: disconnection times met, 30 mA RCD on every final circuit, and every extraneous-conductive-part tied into main bonding. Miss one, you bond.

Single-page A4 field noticeboard specification
BS 7671:2018+A4:2026 §701.32Spatial Boundary Geometry (Architectural Cross-Section)
Architectural Cross-Section of Bathroom Zones BS 7671 Section 701OUTSIDE ZONES (BS 7671:2018+A4:2026 §701.32)Standard 230 V 13 A Socket-Outlets permitted strictly ≥ 2.5 m horizontally from Zone 1 boundary (Reg 701.512.3)ZONE 20.60 mHorizontal WidthUp to 2.25 m heightMin IPX4Shaver supply unitto BS EN 61558-2-5 OKZONE 1Over Bath / Shower BasinUp to 2.25 m above FFL (or highest shower head)Min IPX4IPX5 (Jets)30 mA RCD Mandatory (Reg 701.411.3.3)Fixed water heaters, showers & SELV ≤ 12 V onlyZONE 0Interior of Bath Tub / Shower BasinMin IPX7 SubmersionSELV ≤ 12 V AC RMS / 30 V DC onlyZONE 20.60 mHorizontal WidthUp to 2.25 m heightMin IPX4Shaver supply unitto BS EN 61558-2-5 OK2.25 m HEIGHT ABOVE FFL (§701.32.3)230 V Switched Socket≥ 2.5 m from Zone 1(Reg 701.512.3)∇ 0.000m FFL • FINISHED FLOOR LEVEL DATUM0.60 mBath / Tray Envelope0.60 m
ZONE 1Zone 1: Space Directly Over Bath / Shower Basin
MANDATORY IP:IPX4 / IPX5
Permitted Equipment:

Fixed water heaters, showers, luminaires, and SELV accessories (12V AC / 30V DC).

Prohibited Switchgear:

Standard 230V socket-outlets, light switches, and isolators strictly prohibited.

SELV & Voltage Limits:

Max 12 V AC rms / 30 V ripple-free DC. Safety source must reside outside Zones 0 and 1.

RCD Requirement:

30 mA RCD mandatory on all low-voltage circuits (Reg 701.411.3.3).

2.5m Socket Distance Validator (Reg 701.512.3)Verify minimum horizontal distance from Zone 1 boundary
metres
Measured horizontally from the vertical plane bordering Zone 1.
PASS: Meets Regulation 701.512.3 dimension

Standard 230 V 13 A socket-outlets permitted with 30 mA RCD protection when positioned at least 2.5 m horizontally from the Zone 1 boundary.

Table 4: Section 701 Zoning Boundaries & Mandatory Equipment Ingress Protection • Verified 2026-11-01
Zone DesignationDimensional BoundaryMin IPPermitted Equipment & SwitchgearRCD & SELV Rules
Zone 0INTERIOR OF BASIN / TRAYInterior of the bath tub or shower basin. For showers without a basin, height of 100 mm above finished floor level extending to 1.20 m from fixed water outlet.
IPX7 General
IPX5 Water jets
Prohibited entirely. No switches, accessories, or socket-outlets permitted under any circumstance. Only fixed equipment specifically designed for Zone 0 complying with relevant product standards, suitable for Zone 0 per manufacturer instructions, fixed and permanently connected (Reg 701.55).SELV only, maximum 12 V AC rms or 30 V ripple-free DC. Safety source must reside outside Zones 0 and 1.
Zone 1WATER SPRAY RISK REGIONAbove the bath tub or shower tray up to a height of 2.25 m above finished floor level, or the highest fixed shower head if higher. Space under bath is Zone 1 unless accessible only with a tool.
IPX4 General
IPX5 Water jets
Only switches of SELV circuits up to 12 V AC or 30 V DC with safety source outside Zones 0 and 1. Insulated pull cords permitted. Fixed water heaters, showers, shower pumps, and luminaires suitable for Zone 1 and manufacturer-certified for wet locations.SELV or PELV up to 25 V AC rms or 60 V ripple-free DC for equipment. Switchgear restricted to SELV 12 V AC or 30 V DC.
Zone 20.60m SPLASH PERIMETERRegion immediately outside Zone 1 extending 0.60 m horizontally and up to 2.25 m above finished floor level.
IPX4 General
IPX5 Water jets
Switchgear, accessories incorporating switches, and socket-outlets prohibited, except switches and contacts of SELV circuits (safety source outside Zones 0 and 1) and shaver supply units to BS EN 61558-2-5 (Reg 701.512.3). Insulated pull cords permitted. Luminaires, ventilation fans, towel rails, and Class I or Class II equipment suitable for Zone 2 conditions.Standard low voltage permitted where protected by 30 mA RCD under Regulation 701.411.3.3, SELV, or PELV.
Outside ZonesROOM ENVELOPEAny area within the room containing a bath or shower that sits beyond Zone 0, Zone 1, and Zone 2, and above Zone 1 and 2 height (2.25 m or highest fixed shower head).
IPX0 General
IPX5 Water jets
Standard 230 V 13 A socket-outlets permitted strictly at or beyond 2.5 m horizontally from the boundary of Zone 1 (Reg 701.512.3). Socket-outlets other than SELV or shaver units prohibited within 2.5 m of Zone 1. Standard equipment suitable for general domestic and commercial locations.Standard 230 V single-phase supply. Every low voltage final circuit requires 30 mA RCD protection under Regulation 701.411.3.3.

Supplementary Equipotential Bonding Exemption (Reg 701.415.2)

Local supplementary equipotential bonding in bathrooms may be omitted ONLY IF ALL THREE of the following conditions are verified:

Condition 1 of 3(Reg 701.415.2 (i))
Automatic Disconnection Verified

All final circuits of the location comply with the requirements for automatic disconnection of supply according to Regulation 411.3.2.

Condition 2 of 3(Reg 701.415.2 (ii))
30 mA RCD Additional Protection

All final circuits of the location have additional protection by means of a 30 mA RCD complying with Regulation 415.1.1 and Regulation 701.411.3.3.

Condition 3 of 3(Reg 701.415.2 (iii))
Extraneous Continuity to Main Bonding

All extraneous-conductive-parts of the location are effectively connected to the protective equipotential bonding according to Regulation 411.3.1.2.

BS 7671:2018+A4:2026 Part 2 & Chapter 54Electricity Safety, Quality and Continuity Regulations 2002 Reg 9

3. Earthing Systems Quick-Comparison Matrix

Comprehensive comparison of UK supply earthing arrangements: TN-S, TN-C-S (PME), and TT systems, including maximum typical source impedances, main bonding rules, and broken neutral hazards.

Bench Mentor Note: On-Site Decision Making

Earthing first, paperwork second. Look at the cutout. A separate earth clamp on the cable sheath suggests TN-S; an earth terminal off the neutral block, often with a PME label, means TN-C-S; no supplier earth at all means TT with a rod. Then measure Ze and compare it with the DNO declared maximum: 0.80 ohms for TN-S and 0.35 ohms for PME. Above that, stop and investigate. On PME, remember a broken PEN conductor can lift every bonded metal part to dangerous voltage. On PME, size main protective bonding from Table 54.8; on TN-S and TT, size it from Regulation 544.1.1.

Single-page A4 field noticeboard specification
TN-S

Separate Neutral & Earth (TN-S)

Typical Max Source Ze (Declared)
0.80Ω
Declared DNO typical maximum source impedance0.80 Ω (Declared DNO typical maximum)
Earth Return Path

Dedicated metallic cable sheath, lead armouring, or separate continuous earth conductor back to substation star point.

Main Protective Bonding

Reg 544.1.1: Sized at not less than half the required earthing conductor CSA, minimum 6 mm² copper, and need not exceed 25 mm² copper. Table 54.8 does not apply.

Protective Devices (ADS)

Circuit-breakers and fuses provide Automatic Disconnection of Supply (ADS) due to low loop impedance. RCD optional for fault protection, mandatory for additional protection.

Hazard & Risk Analysis

Risk Analysis: Ageing lead sheath cables can corrode or lose continuous metallic contact over decades, causing elevated Ze without visual indication until tested.

TN-C-S / PME

Protective Multiple Earthing (PME / TN-C-S)

Typical Max Source Ze (Declared)
0.35Ω
Declared DNO typical maximum source impedance0.35 Ω (Declared DNO typical maximum)
Earth Return Path

Supply PEN conductor earthed at multiple points along the distribution main by the DNO before reaching consumer premises.

Main Protective Bonding

BS 7671 Table 54.8: Sized strictly according to the copper equivalent CSA of the supply neutral (10 mm² Cu for neutral ≤ 35 mm²; 16 mm² Cu for neutral 35 to 50 mm²; up to 50 mm² Cu maximum cap).

Protective Devices (ADS)

Circuit-breakers and fuses provide exceptionally fast ADS due to very low source loop impedance.

Hazard & Risk Analysis

Risk Analysis: Broken PEN hazard: If the incoming supply PEN conductor is severed or broken, diverted neutral load current flows through installation bonding and extraneous pipework, elevating exposed metalwork to dangerous touch voltages.

TT

Earth Electrode System (TT)

Typical Max Source Ze (Declared)
21Ω
Nominal DNO substation source (RA typically < 200 Ω per IET GN3)21 Ω (Nominal DNO substation source) • Local electrode RA typically < 200 Ω per IET GN3
Earth Return Path

Local consumer earth electrode (copper rod, earth plate, or foundation mesh) through the general mass of earth to the substation star point electrode.

Main Protective Bonding

Reg 544.1.1: Sized at not less than half the required earthing conductor CSA, minimum 6 mm² copper, and need not exceed 25 mm² copper. Table 54.8 does not apply.

Protective Devices (ADS)

RCD mandatory for fault protection (ADS) under Regulation 411.5.2 and Table 41.5 (RA × IΔn ≤ 50 V). Overcurrent protective devices cannot achieve ADS with high earth loop impedance.

Hazard & Risk Analysis

Risk Analysis: High earth loop impedance Ze prevents circuit-breakers and fuses from tripping under earth faults. Complete safety reliance on operational integrity of RCDs. Soil resistance varies with seasonal freezing and drought.

Earthing Diagnostics & Main Bonding Sizing EngineSelect supply earthing arrangement to calibrate Ze limits and calculate required copper bonding conductor size

1. Source Loop Impedance (Ze) Threshold & PFC Engine

Compares measured on-site Ze against DNO limits and calculates prospective fault current.

Ω
PASS: Within DNO Declared Maximum

Measured Ze (0.30 Ω) complies with the DNO declared maximum limit of 0.35 Ω for TN-C-S supplies.

Prospective Fault Current (Ipf = U0 / Ze):Nominal U0 = 230 V line to earth
0.66kA
Within 6 kA standard domestic switchgear breaking capacity

2. Main Protective Bonding Sizing Calculator

BS 7671 Table 54.8 (PME) & Regulation 544.1.1 (TN-S / TT).

10 mm²Minimum Copper Conductor CSA

BS 7671 Table 54.8: 10 mm² copper required for supply neutral ≤ 35 mm².

DNO Notice: Local network rules may specify 16 mm² minimum

Main Protective Bonding Sizing (BS 7671 Table 54.8 for PME)

Table 5: Minimum Cross-Sectional Area of Main Protective Bonding Conductor for PME (TN-C-S) Supplies • Verified 2026-11-01
Copper Equivalent CSA of Supply NeutralMin Copper Conductor CSAMin Aluminium Conductor CSAApplication Context
S ≤ 35 mm²10 mm²25 mm²Standard domestic and small commercial supplies (up to 100 A single-phase cutouts).
35 mm² < S ≤ 50 mm²16 mm²35 mm²Commercial three-phase TP&N supplies (typically 125 A to 200 A cutouts).
50 mm² < S ≤ 95 mm²25 mm²50 mm²Medium commercial and industrial supplies (typically 250 A to 400 A).
95 mm² < S ≤ 150 mm²35 mm²70 mm²Heavy commercial and light industrial supplies (up to 630 A distribution).
S > 150 mm²50 mm²95 mm²Heavy industrial switchboards and private substation transformer fed installations (50 mm² Cu maximum cap).

Statutory & BS 7671 Restrictions on PME Earthing

PME (TN-C-S) earth terminals must NOT be exported or used for the following installations without dedicated statutory mitigation:

Electric Vehicle Outdoor Charging (Section 722)(BS 7671 Reg 722.411.4.1)

Risk of touch potential between vehicle body and true earth (the general mass of Earth) during open-PEN supply fault.

MITIGATION: Prohibited from exporting PME earth unless using open-PEN automated disconnect device, dedicated TT earth electrode, or isolation transformer.
Petrol Filling Stations & DSEAR Hazardous Areas(APEA/EI Blue Book & DSEAR 2002 Reg 6)

Circulating stray earth currents through underground metallic fuel storage tanks and forecourt pipework can cause ignition arcs.

MITIGATION: PME earth must never be connected to forecourt hazardous areas. Dedicated TT or separate TN-S earthing arrangement required.
Agricultural & Horticultural Installations (Section 705)(BS 7671 Reg 705.411.1)

Livestock touch voltage sensitivity is reduced to 25 V AC due to large body size and wet floor or earth contact.

MITIGATION: PME earth prohibited in livestock housing. Installation must convert to TT system with 30 mA RCD protection.
Caravan Parks & Marinas (Section 708 & 709)(BS 7671 Reg 708.411.4 // Reg 709.411.4 & ESQCR Reg 9(4))

Risk of open-PEN voltage transfer onto caravan metal chassis or submerged boat hulls.

MITIGATION: PME earth must not be exported to individual caravan hookup pitches or pontoon supply bollards. TT supply mandatory.
BS 7671:2018+A4:2026 Chapter 41SI 1989 No. 635 (as amended)

4. Maximum Disconnection Times Reference Deck

Maximum operating times for protective devices under Automatic Disconnection of Supply (ADS) in accordance with BS 7671:2018+A4:2026 Chapter 41.

Bench Mentor Note: On-Site Decision Making

Know your boundary. Reg 411.3.2.2 puts Table 41.1 times on final circuits up to 63 A with socket-outlets, and up to 32 A supplying only fixed equipment. That means 0.4 s on TN and 0.2 s on TT at 230 V. Fixed equipment over 32 A and distribution circuits get 5.0 s on TN under Reg 411.3.2.3, but only 1.0 s on TT under Reg 411.3.2.4. And a 400 V three-phase circuit is still U0 230 V to earth. Use the 230 V row, not the stricter one. Get it wrong and you will chase needlessly tight limits.

Single-page A4 field noticeboard specification
Calibrated Disconnection Time Instrument (ADS)Select System, Circuit Type, and Nominal Voltage U0 to calculate maximum permitted trip time under BS 7671
UK standard 230V 1-phase and 400V 3-phase circuits have U0 = 230V line-to-earth.
0.4seconds
Final Circuit (ADS Table 41.1)
Standard Citation:BS 7671 Table 41.1 & Reg 411.3.2.2
Application Scope:Final circuits not exceeding 63 A with socket-outlets, and not exceeding 32 A supplying only fixed equipment.
Max Permitted Zs:1.37 Ω (Tabulated at 70°C) •1.09 Ω (0.8 Rule-of-Thumb ambient test limit)
RCD Trip Limits:1× IΔn ≤ 300 ms • 5× IΔn ≤ 40 ms (General RCD)
STATUTORY DUTY: EAWR 1989 Regulation 8 (Earthing) and Regulation 11 (Excess Current Protection).
Table 6: BS 7671 Table 41.1 Maximum Disconnection Times for Final & Distribution Circuits • Verified 2026-11-01
Nominal Voltage (U0)Final Circuits (TN System)Final Circuits (TT System)Distribution & Fixed > 32AStandard Reference
50 V < U0 ≤ 120 V ACU0 = 120 V (Line to Earth)0.8 s0.3 sTN: 5.0 s / TT: 1.0 sTable 41.1 & Reg 411.3.2.2
120 V < U0 ≤ 230 V ACU0 = 230 V (Line to Earth)0.4 s0.2 sTN: 5.0 s / TT: 1.0 sTable 41.1 & Reg 411.3.2.2
230 V < U0 ≤ 400 V ACU0 = 400 V (Line to Earth)0.2 s0.07 sTN: 5.0 s / TT: 1.0 sTable 41.1 & Reg 411.3.2.2
U0 > 400 V ACU0 > 400 V (Line to Earth)0.1 s0.04 sTN: 5.0 s / TT: 1.0 sTable 41.1 & Reg 411.3.2.2
120 V < U0 ≤ 230 V DCU0 = 230 V DC5.0 s0.4 sTN: 5.0 s / TT: 1.0 sTable 41.1 (DC)
Reduced Low Voltage (110 V CTE Construction Supplies)110 V single-phase centre-tapped to earth (U0 = 55 V to earth) or 110 V three-phase (U0 = 63.5 V to earth)5.0 s5.0 s (Centre-tapped earth)5.0 sReg 411.8.3
Reg 411.3.2.2

Table 41.1 Final Circuit Scope

Mandatory for final circuits not exceeding 63 A with one or more socket-outlets, and final circuits not exceeding 32 A supplying only fixed connected current-using equipment. Permitted: 0.4 s (TN) / 0.2 s (TT) at 230 V

Reg 411.3.2.3

Distribution Circuits (TN Systems)

Permitted for distribution circuits and final circuits exceeding 32 A supplying only fixed equipment (where no socket-outlets are connected). Permitted: 5.0 seconds

Reg 411.3.2.4

Distribution Circuits (TT Systems)

Permitted for distribution circuits and final circuits exceeding 32 A supplying only fixed equipment in TT systems. Permitted: 1.0 second

Reg 411.3.3

Socket-Outlets ≤ 32 A Mandatory RCD

Socket-outlets with rated current not exceeding 32 A in locations where they may be used by ordinary persons require 30 mA RCD additional protection. Permitted: 300 ms max trip at 1× IΔn

Reg 411.5.3 / Table 41.5

TT Touch Voltage Limit: RA × IΔn ≤ 50 V

On TT systems, earth loop impedance Ze is too high for circuit-breakers to achieve Table 41.1 times. Fault protection is provided by RCDs. Under Regulation 411.5.3, the condition RA × IΔn ≤ 50 V must be satisfied, and Zs must satisfy Table 41.5 with the Table 41.1 disconnection time met. Limit: 50 V AC rms

Need to calculate circuit parameters?

Use our interactive BS 7671 calculators for Max Zs, Cable Sizing, and Motor Current.