Pocket Electrical Cheat Sheets
Field-ready reference tables and interactive lookup tools calibrated to BS 7671:2018+A4:2026, BS EN 60529, and UK statutory standards. Designed for high-speed verification on phones, tablets, and field test instruments.
1. Ingress Protection (IP Code) Reference Deck
Pick an enclosure rating for adverse, wet, or dusty environments. An IP rating defines sealing effectiveness against solid foreign bodies and moisture under BS EN 60529. Verify statutory minimums under BS 7671 and the Electricity at Work Regulations 1989.
Bench Mentor Note: Statutory Law vs Consensus Standards
Regulation 6 of the Electricity at Work Regulations 1989 is statutory criminal law. It mandates that any electrical equipment exposed to weather, wet, dirty, or corrosive conditions must be constructed or protected to prevent danger.
BS 7671 (IET Wiring Regulations) and BS EN 60529 are non-statutory consensus standards. Conformity with these standards is deemed to satisfy the statutory safety duties of EAWR Regulation 6, but the standards themselves carry no direct criminal force.
| Digit | Object Size | Hazardous Contact Access | Test Method & Acceptance |
|---|---|---|---|
| 0 | None | No protection against contact | No test applied |
| 1 | >= 50 mm | Back of hand (IP1X / IPXXA) | 50 mm rigid sphere probe with 50 N force |
| 2 | >= 12.5 mm | Finger safe (IP2X / IPXXB) | 12.5 mm articulated test finger probe with 30 N force |
| 3 | >= 2.5 mm | Tool protected (IP3X / IPXXC) | 2.5 mm test rod with 3 N force |
| 4 | >= 1.0 mm | Wire safe (IP4X / IPXXD) | 1.0 mm rigid steel wire probe with 1 N force |
| 5 | Dust protected | Complete contact prevention | Talcum powder circulation under depression for 8 hours (limited ingress) |
| 6 | Dust tight | Complete contact prevention | Talcum powder circulation under depression for 8 hours (zero ingress) |
| X | Unspecified | Unspecified | No test declared |
| Digit | Protection Level | Test Parameters | Cumulative Status |
|---|---|---|---|
| 0 | No Protection | No test applied | Cumulative |
| 1 | Vertically Dripping Water | Dripping box 1 mm/min for 10 min | Cumulative |
| 2 | Dripping Water Tilted 15 Degrees | Dripping box 3 mm/min for 2.5 min per 4 fixed tilt positions | Cumulative |
| 3 | Spraying Water (Rainproof) | Oscillating tube or spray nozzle up to 60 degrees from vertical at 10 l/min for 10 min | Cumulative |
| 4 | Splashing Water (Splashproof) | Oscillating tube 360 degrees or spray nozzle with shield removed at 10 l/min for 10 min | Cumulative |
| 5 | Water Jets | 6.3 mm nozzle delivering 12.5 l/min at 30 kPa core pressure from 2.5 to 3 m for 3 min | Cumulative |
| 6 | Powerful Water Jets | 12.5 mm nozzle delivering 100 l/min at 100 kPa core pressure from 2.5 to 3 m for 3 min | Cumulative |
| 7 | Temporary Immersion | Submersion in water 0.15 m to 1.0 m depth for 30 minutes | Non-cumulative (Jets not implied) |
| 8 | Continuous Submersion | Continuous submersion under manufacturer specified pressure or depth | Non-cumulative (Jets not implied) |
| 9 | High-Pressure High-Temperature Water Jets | Fan and point nozzles delivering 14 to 16 l/min at 80 degrees C and 8 to 10 MPa (80 to 100 bar) at 0, 30, 60, 90 degrees | Non-cumulative (Jets not implied) |
| X | Not Declared | No test declared | Cumulative |
| Installation Location / Apparatus | Min IP Rating | Regulation / Clause | Legal Status | Operational Notes |
|---|---|---|---|---|
| Enclosure top horizontal surfaces | IP4X or IPXXD | BS 7671 Reg 416.2.2 | ● Standard | No entry of 1.0 mm wire probe. Mandatory for readily accessible top surfaces of distribution boards and consumer units. |
| Enclosure accessible vertical surfaces | IP2X or IPXXB | BS 7671 Reg 416.2.1 | ● Standard | No finger contact with hazardous live parts (jointed 80 mm test probe, 12 mm diameter). |
| Outdoor EV charge points | IP44 minimum | BS 7671 Reg 722.512.2BS EN 60529 Clause 6 | ● Standard | Dust protected against foreign bodies > 1.0 mm and splashing water. Higher ratings such as IP54 or IP65 are common manufacturer options but IP44 is the statutory minimum standard. |
| Underground joint boxes and cable pits | IP68 | BS 7671 Reg 522.3BS EN 60529 Clause 6 | ● Standard | Presence of water external influence AD. Continuous submersion under head of water. Resin or gel filled enclosure. |
| Bathroom Zone 0 (interior of bath or shower basin) | IPX7 | BS 7671 Reg 701.512.2 | ● Standard | Protected against temporary immersion to 1 m depth. SELV not exceeding 12 V AC rms or 30 V ripple-free DC only. |
| Bathroom Zone 1 and Zone 2 (general locations) | IPX4 | BS 7671 Reg 701.512.2 | ● Standard | Splashproof from any direction. 30 mA RCD protection mandatory on all circuits supplying the location. |
| Bathroom Zone 1 and Zone 2 (cleaning jets used) | IPX5 | BS 7671 Reg 701.512.2 | ● Standard | Required where water jets are used for cleaning, such as communal showers, sports facilities, and commercial washrooms. |
| External domestic socket outlets | IP66 closed / IP56 in-use | BS 7671 Reg 512.2 | ● Standard | External influences AD4 (water splashes or jets) and AE3 (small foreign bodies). Enclosure must maintain seal with standard 13 A plug inserted. |
| Adverse and wet environments (statutory baseline) | Suitable construction and sealing | EAWR 1989 Reg 6 | ◆ Statute | Criminal statutory duty. Electrical equipment exposed to weather, natural hazards, wet, dirty, or corrosive conditions must be constructed or protected to prevent danger. |
IPX9K vs IPX9 (BS EN 60529)Engineering Demarcation (ISO 20653)
IPX9K originates from road vehicle standard ISO 20653 (originally DIN 40050-9) for high-pressure washdown of automotive equipment. BS EN 60529 defines IPX9 for industrial enclosures with slightly different nozzle distances and pressure limits. The two standards are distinct and not interchangeable in statutory specifications.
2. Bathroom & Shower Zones Spatial Reference
Locations containing a bath or shower present increased shock risk due to reduced skin resistance in wet contact. Section 701 prescribes rigorous zone boundaries, equipment restrictions, and protective measures.
Bench Mentor Note: On-Site Decision Making
Right, bathrooms. Measure every socket position horizontally from the Zone 1 boundary, not from the bath edge or the door. Under Reg 701.512.3, standard socket-outlets require at least 2.5 m separation from Zone 1. Every circuit serving the room needs 30 mA RCD protection, so test it, do not assume it. Before you skip supplementary bonding under Reg 701.415.2, prove all three: disconnection times met, 30 mA RCD on every final circuit, and every extraneous-conductive-part tied into main bonding. Miss one, you bond.
Fixed water heaters, showers, luminaires, and SELV accessories (12V AC / 30V DC).
Standard 230V socket-outlets, light switches, and isolators strictly prohibited.
Max 12 V AC rms / 30 V ripple-free DC. Safety source must reside outside Zones 0 and 1.
30 mA RCD mandatory on all low-voltage circuits (Reg 701.411.3.3).
Standard 230 V 13 A socket-outlets permitted with 30 mA RCD protection when positioned at least 2.5 m horizontally from the Zone 1 boundary.
| Zone Designation | Dimensional Boundary | Min IP | Permitted Equipment & Switchgear | RCD & SELV Rules |
|---|---|---|---|---|
| Zone 0INTERIOR OF BASIN / TRAY | Interior of the bath tub or shower basin. For showers without a basin, height of 100 mm above finished floor level extending to 1.20 m from fixed water outlet. | IPX7 General IPX5 Water jets | Prohibited entirely. No switches, accessories, or socket-outlets permitted under any circumstance. Only fixed equipment specifically designed for Zone 0 complying with relevant product standards, suitable for Zone 0 per manufacturer instructions, fixed and permanently connected (Reg 701.55). | SELV only, maximum 12 V AC rms or 30 V ripple-free DC. Safety source must reside outside Zones 0 and 1. |
| Zone 1WATER SPRAY RISK REGION | Above the bath tub or shower tray up to a height of 2.25 m above finished floor level, or the highest fixed shower head if higher. Space under bath is Zone 1 unless accessible only with a tool. | IPX4 General IPX5 Water jets | Only switches of SELV circuits up to 12 V AC or 30 V DC with safety source outside Zones 0 and 1. Insulated pull cords permitted. Fixed water heaters, showers, shower pumps, and luminaires suitable for Zone 1 and manufacturer-certified for wet locations. | SELV or PELV up to 25 V AC rms or 60 V ripple-free DC for equipment. Switchgear restricted to SELV 12 V AC or 30 V DC. |
| Zone 20.60m SPLASH PERIMETER | Region immediately outside Zone 1 extending 0.60 m horizontally and up to 2.25 m above finished floor level. | IPX4 General IPX5 Water jets | Switchgear, accessories incorporating switches, and socket-outlets prohibited, except switches and contacts of SELV circuits (safety source outside Zones 0 and 1) and shaver supply units to BS EN 61558-2-5 (Reg 701.512.3). Insulated pull cords permitted. Luminaires, ventilation fans, towel rails, and Class I or Class II equipment suitable for Zone 2 conditions. | Standard low voltage permitted where protected by 30 mA RCD under Regulation 701.411.3.3, SELV, or PELV. |
| Outside ZonesROOM ENVELOPE | Any area within the room containing a bath or shower that sits beyond Zone 0, Zone 1, and Zone 2, and above Zone 1 and 2 height (2.25 m or highest fixed shower head). | IPX0 General IPX5 Water jets | Standard 230 V 13 A socket-outlets permitted strictly at or beyond 2.5 m horizontally from the boundary of Zone 1 (Reg 701.512.3). Socket-outlets other than SELV or shaver units prohibited within 2.5 m of Zone 1. Standard equipment suitable for general domestic and commercial locations. | Standard 230 V single-phase supply. Every low voltage final circuit requires 30 mA RCD protection under Regulation 701.411.3.3. |
Supplementary Equipotential Bonding Exemption (Reg 701.415.2)
Local supplementary equipotential bonding in bathrooms may be omitted ONLY IF ALL THREE of the following conditions are verified:
All final circuits of the location comply with the requirements for automatic disconnection of supply according to Regulation 411.3.2.
All final circuits of the location have additional protection by means of a 30 mA RCD complying with Regulation 415.1.1 and Regulation 701.411.3.3.
All extraneous-conductive-parts of the location are effectively connected to the protective equipotential bonding according to Regulation 411.3.1.2.
3. Earthing Systems Quick-Comparison Matrix
Comprehensive comparison of UK supply earthing arrangements: TN-S, TN-C-S (PME), and TT systems, including maximum typical source impedances, main bonding rules, and broken neutral hazards.
Bench Mentor Note: On-Site Decision Making
Earthing first, paperwork second. Look at the cutout. A separate earth clamp on the cable sheath suggests TN-S; an earth terminal off the neutral block, often with a PME label, means TN-C-S; no supplier earth at all means TT with a rod. Then measure Ze and compare it with the DNO declared maximum: 0.80 ohms for TN-S and 0.35 ohms for PME. Above that, stop and investigate. On PME, remember a broken PEN conductor can lift every bonded metal part to dangerous voltage. On PME, size main protective bonding from Table 54.8; on TN-S and TT, size it from Regulation 544.1.1.
Separate Neutral & Earth (TN-S)
Dedicated metallic cable sheath, lead armouring, or separate continuous earth conductor back to substation star point.
Reg 544.1.1: Sized at not less than half the required earthing conductor CSA, minimum 6 mm² copper, and need not exceed 25 mm² copper. Table 54.8 does not apply.
Circuit-breakers and fuses provide Automatic Disconnection of Supply (ADS) due to low loop impedance. RCD optional for fault protection, mandatory for additional protection.
Risk Analysis: Ageing lead sheath cables can corrode or lose continuous metallic contact over decades, causing elevated Ze without visual indication until tested.
Protective Multiple Earthing (PME / TN-C-S)
Supply PEN conductor earthed at multiple points along the distribution main by the DNO before reaching consumer premises.
BS 7671 Table 54.8: Sized strictly according to the copper equivalent CSA of the supply neutral (10 mm² Cu for neutral ≤ 35 mm²; 16 mm² Cu for neutral 35 to 50 mm²; up to 50 mm² Cu maximum cap).
Circuit-breakers and fuses provide exceptionally fast ADS due to very low source loop impedance.
Risk Analysis: Broken PEN hazard: If the incoming supply PEN conductor is severed or broken, diverted neutral load current flows through installation bonding and extraneous pipework, elevating exposed metalwork to dangerous touch voltages.
Earth Electrode System (TT)
Local consumer earth electrode (copper rod, earth plate, or foundation mesh) through the general mass of earth to the substation star point electrode.
Reg 544.1.1: Sized at not less than half the required earthing conductor CSA, minimum 6 mm² copper, and need not exceed 25 mm² copper. Table 54.8 does not apply.
RCD mandatory for fault protection (ADS) under Regulation 411.5.2 and Table 41.5 (RA × IΔn ≤ 50 V). Overcurrent protective devices cannot achieve ADS with high earth loop impedance.
Risk Analysis: High earth loop impedance Ze prevents circuit-breakers and fuses from tripping under earth faults. Complete safety reliance on operational integrity of RCDs. Soil resistance varies with seasonal freezing and drought.
1. Source Loop Impedance (Ze) Threshold & PFC Engine
Compares measured on-site Ze against DNO limits and calculates prospective fault current.
Measured Ze (0.30 Ω) complies with the DNO declared maximum limit of 0.35 Ω for TN-C-S supplies.
2. Main Protective Bonding Sizing Calculator
BS 7671 Table 54.8 (PME) & Regulation 544.1.1 (TN-S / TT).
BS 7671 Table 54.8: 10 mm² copper required for supply neutral ≤ 35 mm².
DNO Notice: Local network rules may specify 16 mm² minimumMain Protective Bonding Sizing (BS 7671 Table 54.8 for PME)
| Copper Equivalent CSA of Supply Neutral | Min Copper Conductor CSA | Min Aluminium Conductor CSA | Application Context |
|---|---|---|---|
| S ≤ 35 mm² | 10 mm² | 25 mm² | Standard domestic and small commercial supplies (up to 100 A single-phase cutouts). |
| 35 mm² < S ≤ 50 mm² | 16 mm² | 35 mm² | Commercial three-phase TP&N supplies (typically 125 A to 200 A cutouts). |
| 50 mm² < S ≤ 95 mm² | 25 mm² | 50 mm² | Medium commercial and industrial supplies (typically 250 A to 400 A). |
| 95 mm² < S ≤ 150 mm² | 35 mm² | 70 mm² | Heavy commercial and light industrial supplies (up to 630 A distribution). |
| S > 150 mm² | 50 mm² | 95 mm² | Heavy industrial switchboards and private substation transformer fed installations (50 mm² Cu maximum cap). |
Statutory & BS 7671 Restrictions on PME Earthing
PME (TN-C-S) earth terminals must NOT be exported or used for the following installations without dedicated statutory mitigation:
Risk of touch potential between vehicle body and true earth (the general mass of Earth) during open-PEN supply fault.
Circulating stray earth currents through underground metallic fuel storage tanks and forecourt pipework can cause ignition arcs.
Livestock touch voltage sensitivity is reduced to 25 V AC due to large body size and wet floor or earth contact.
Risk of open-PEN voltage transfer onto caravan metal chassis or submerged boat hulls.
4. Maximum Disconnection Times Reference Deck
Maximum operating times for protective devices under Automatic Disconnection of Supply (ADS) in accordance with BS 7671:2018+A4:2026 Chapter 41.
Bench Mentor Note: On-Site Decision Making
Know your boundary. Reg 411.3.2.2 puts Table 41.1 times on final circuits up to 63 A with socket-outlets, and up to 32 A supplying only fixed equipment. That means 0.4 s on TN and 0.2 s on TT at 230 V. Fixed equipment over 32 A and distribution circuits get 5.0 s on TN under Reg 411.3.2.3, but only 1.0 s on TT under Reg 411.3.2.4. And a 400 V three-phase circuit is still U0 230 V to earth. Use the 230 V row, not the stricter one. Get it wrong and you will chase needlessly tight limits.
| Nominal Voltage (U0) | Final Circuits (TN System) | Final Circuits (TT System) | Distribution & Fixed > 32A | Standard Reference |
|---|---|---|---|---|
| 50 V < U0 ≤ 120 V ACU0 = 120 V (Line to Earth) | 0.8 s | 0.3 s | TN: 5.0 s / TT: 1.0 s | Table 41.1 & Reg 411.3.2.2 |
| 120 V < U0 ≤ 230 V ACU0 = 230 V (Line to Earth) | 0.4 s | 0.2 s | TN: 5.0 s / TT: 1.0 s | Table 41.1 & Reg 411.3.2.2 |
| 230 V < U0 ≤ 400 V ACU0 = 400 V (Line to Earth) | 0.2 s | 0.07 s | TN: 5.0 s / TT: 1.0 s | Table 41.1 & Reg 411.3.2.2 |
| U0 > 400 V ACU0 > 400 V (Line to Earth) | 0.1 s | 0.04 s | TN: 5.0 s / TT: 1.0 s | Table 41.1 & Reg 411.3.2.2 |
| 120 V < U0 ≤ 230 V DCU0 = 230 V DC | 5.0 s | 0.4 s | TN: 5.0 s / TT: 1.0 s | Table 41.1 (DC) |
| Reduced Low Voltage (110 V CTE Construction Supplies)110 V single-phase centre-tapped to earth (U0 = 55 V to earth) or 110 V three-phase (U0 = 63.5 V to earth) | 5.0 s | 5.0 s (Centre-tapped earth) | 5.0 s | Reg 411.8.3 |
Table 41.1 Final Circuit Scope
Mandatory for final circuits not exceeding 63 A with one or more socket-outlets, and final circuits not exceeding 32 A supplying only fixed connected current-using equipment. Permitted: 0.4 s (TN) / 0.2 s (TT) at 230 V
Distribution Circuits (TN Systems)
Permitted for distribution circuits and final circuits exceeding 32 A supplying only fixed equipment (where no socket-outlets are connected). Permitted: 5.0 seconds
Distribution Circuits (TT Systems)
Permitted for distribution circuits and final circuits exceeding 32 A supplying only fixed equipment in TT systems. Permitted: 1.0 second
Socket-Outlets ≤ 32 A Mandatory RCD
Socket-outlets with rated current not exceeding 32 A in locations where they may be used by ordinary persons require 30 mA RCD additional protection. Permitted: 300 ms max trip at 1× IΔn
TT Touch Voltage Limit: RA × IΔn ≤ 50 V
On TT systems, earth loop impedance Ze is too high for circuit-breakers to achieve Table 41.1 times. Fault protection is provided by RCDs. Under Regulation 411.5.3, the condition RA × IΔn ≤ 50 V must be satisfied, and Zs must satisfy Table 41.5 with the Table 41.1 disconnection time met. Limit: 50 V AC rms