← Back to Tools DirectoryFault Current Guide →

Adiabatic Equation Calculator

Under BS 7671 Regulation 543.1.3, the circuit protective conductor (CPC) must withstand the thermal energy let-through (I²t) of the protective device during a fault without exceeding the insulation's maximum temperature limit. Rather than acting as a black box, this tool evaluates the adiabatic equation from first principles, shows the intermediate energy let-through, and verifies existing CPC suitability.

Plant-Room Ready: This calculator caches to your phone and works 100% offline with zero mobile signal. Add to your home screen for quick access on site.
1. Fault Parameters
Presets:
2. Conductor Material & k Factor
3. Existing Conductor Check (Optional)

Calculation Summary

Reg 543.1.3 Live Calculation
Minimum Required CPC Area (S)-Theoretical minimum cross-section
Nearest Standard Metric Size-Standard commercial conductor
Energy Let-Through (I²t)-Thermal energy developed

Note on fast-acting devices (t < 0.1 s): The formula S = √(I²t) / k assumes symmetrical current over duration t. For current-limiting devices operating in under 0.1s (such as BS EN 60898 MCBs or BS 88 fuses), use the manufacturer's published energy let-through (I²t) characteristic per Reg 543.1.3 Note 2.

Full 6-Step Adiabatic Design Working

Step 1

Fault Current & Duration Parameters

I = 1,000 A, t = 0.10 s

Prospective fault current flowing through the protective device under short-circuit or earth fault conditions, with the corresponding device operating time.

Step 2

Conductor Thermal Coefficient (k Factor)

k = 115

Factor derived from Table 54.2 for copper conductors with 70°C PVC insulation incorporated in a cable (initial temperature 70°C, final limiting temperature 160°C).

Step 3

Energy Let-Through Calculation (I²t)

I²t = I × I × t

I²t = 1,000² × 0.10 = 100,000 A²s

Thermal energy developed in the conductor during the fault duration.

Step 4

Theoretical Minimum Conductor Area (S)

S = √(I²t) / k

S = √(100,000) / 115 = 316.23 / 115 = 2.75 mm²

Minimum cross-sectional area required to prevent conductor insulation damage or melting.

Step 5

Standard Metric Conductor Size Selection

Selected Standard Size = 4.0 mm²

Rounded up to the next commercially manufactured standard metric conductor size (1.0, 1.5, 2.5, 4.0, 6.0, 10.0, 16.0, 25.0, 35.0, 50.0 mm²).

Step 6

Withstand Capacity Comparison (k²S² ≥ I²t)

Enter an existing CPC in Section 3 to evaluate withstand.

Proves whether the existing conductor possesses sufficient thermal inertia to absorb the fault energy without overheating.

Worked Example & Calculation Breakdown

Scenario: A 32 A radial socket circuit protected by a BS EN 60898 Type B circuit breaker experiences an earth fault at the distribution board. Prospective fault current I = 1,200 A, disconnection time t = 0.1 s, using twin and earth cable with 70°C PVC insulated copper conductors (k = 115 per Table 54.2). The circuit incorporates a 1.5 mm² CPC.

  1. Calculate Energy Let-Through: I²t = 1,200² × 0.1 = 1,440,000 × 0.1 = 144,000 A²s
  2. Calculate Minimum Theoretical CPC: S = √(144,000) / 115 = 379.47 / 115 = 3.30 mm²
  3. Check Existing 1.5 mm² CPC Withstand: k²S² = 115² × 1.5² = 13,225 × 2.25 = 29,756 A²s
  4. Withstand Evaluation: k²S² (29,756 A²s) < I²t (144,000 A²s) ⇒ FAIL. The 1.5 mm² CPC is inadequate for a 1.2 kA fault at 0.1s. An upgraded CPC of at least 4.0 mm² (k²S² = 211,600 A²s) is required.

BS 7671 Regulatory Framework & Limits

⚠️ Engineering design aid: Always verify calculations against the current BS 7671 edition and protective device manufacturer data. Not a substitute for professional design certification.

Frequently Asked Questions

What is the adiabatic equation and when is it required?

The adiabatic equation k²S² ≥ I²t (or S = √(I²t) / k), defined in BS 7671 Regulations 434.5.2 and 543.1.3, calculates the minimum safe cross-sectional area of a conductor or CPC to prevent thermal damage before the protective device disconnects under earth fault or short-circuit current.

What k-factor applies to a standard flat Twin & Earth CPC?

Under BS 7671 Table 54.3, for a 70°C thermoplastic (PVC) copper protective conductor incorporated inside a cable or bunched (such as the bare CPC in 6242Y flat Twin & Earth), k = 115. If the CPC is a separate standalone single-core cable, Table 54.2 specifies k = 143.

What does "adiabatic" mean in electrical engineering?

"Adiabatic" describes a thermodynamic condition where zero heat escapes to the environment. For rapid electrical faults lasting under 5 seconds (especially under 0.1s), all I²t thermal energy is assumed to remain trapped within the copper conductor, meaning the temperature rise depends entirely on conductor mass and material factor k.