Earthing & Main Protective Bonding Sizer

Determine statutory minimum cross-sectional areas for circuit protective conductors (CPCs), earthing conductors, and main protective bonding conductors under BS 7671:2018+A4:2026. Sizes main bonding for PME (Table 54.8) and TN-S / TT (Regulation 544.1.1) supplies, and verifies reduced CPC thermal withstand in Twin & Earth (6242Y) cables via the adiabatic equation (Regulation 543.1.3).

Statutory Verification: Fully checked against BS 7671:2018+A4:2026. Applies the 25 mm² copper cap for TN-S/TT bonding (Reg 544.1.1) and the 50 mm² PME cap (Table 54.8).
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Conductor Sizing Mode
2. Supply Earthing Arrangement

Conductor Sizing Result

Standard Basis: BS 7671:2018+A4:2026 Table 54.8Mode: PME Main Bonding
Minimum Required Conductor SizeTable 54.8 · PME Minimum
10 mm² COPPER
Calculated Minimum10.0 mm²
Standard Cable Size10 mm²
Earthing Conductor10 mm² min
STATUTORY VERDICT:WITHIN LIMIT

For a PME supply with 25 mm² neutral copper equivalent, Table 54.8 mandates a minimum 10 mm² copper main bonding conductor.

0 mm² (No Conductor)Minimum: 10 mm²Statutory Cap: 50 mm²
PME Diverted Neutral Notice:Main bonding conductors in PME installations may carry sustained circulating network neutral currents. Regulation 544.1.1 prohibits sizes below Table 54.8.
Why not 6 mm² or next size down?

Why not 6 mm²? Table 54.8 mandates a strict 10 mm² copper floor for PME supplies to divert circulating diverted neutral currents without overheating.

Conductor Material, Insulation & Cable ConstructionCopper · 70°C PVC · Incorporated
Conductor MaterialDetermines thermal withstand k-factor and copper equivalent conductance.
Conductor Insulation ClassThermal withstand tables 54.2 and 54.3.
Physical ArrangementSeparate conductors permit higher initial cooling before fault.
Cable ConstructionTwin & Earth has reduced CPC; forces thermodynamic adiabatic check.

Glass-Box AM2 Mathematical Derivation Pad

First Principles Verification · BS 7671 Part 5
Regulatory ReferenceStandard FormulaActive SubstitutionCalculated Value
BS 7671 Table 54.8S(bond) from Supply Neutral TierNeutral = 25 mm² (Tails = 25 mm²)10 mm²
BS 7671 Reg 542.3.1 (PME)S(earth) >= S(bond, PME)Earthing conductor must be >= 10 mm²10 mm² min
BS 7671 Reg 544.1.1Minimum Copper FloorPME installation floor requirement10 mm² floor
BS 7671 Reg 544.1.1Statutory Upper CapTable 54.8 Maximum Upper Bound50 mm² max