Back to Tools DirectoryArc Flash Risk Assessment & Arc-Rated PPE Guide

Arc Flash Incident Energy & Boundary Sizer

Arc flash explosions release violent blast pressure and thermal energy capable of causing fatal burns and shrapnel trauma. This tool performs screening calculations per IEEE 1584-2018 to estimate incident energy (cal/cm² and J/cm²), determine the statutory Arc Flash Boundary (AFB), and evaluate protective garment tiers under BS EN 61482-1-1 (ELIM) in accordance with EAWR 1989 Reg 14.

Safety & Compliance Advisory: Regulation 14 of the Electricity at Work Regulations 1989 prohibits work on or near live conductors unless it is unreasonable for them to be dead, reasonable to work live, and suitable precautions are taken. Above 40 cal/cm² (167 J/cm²), blast overpressure shockwaves defeat thermal PPE; under EAWR Reg 14 live working cannot be justified. De-energise upstream to work dead.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. System Voltage & Fault Parameters
Bolted Short-Circuit Current (kA)25.0 kA
Symmetrical RMS fault level from network study or transformer rating.
Protection Arcing Clearing Time (s)0.12 s
Relay trip time plus breaker mechanical opening time.
2. Working Distance & Position
BASIS: IEEE 1584-2018 & BS EN 61482-1-1400V 3Φ · VCB · 457mm
Incident Energy (E) at Working Distance
--.-cal/cm²
Equivalent: --.- J/cm² · Arc Flash Boundary: --.- m
Thermal Hazard & Blast Ceiling5.8 cal/cm² (14.5% of blast ceiling)
0 (Safe)1.2 (Burn)8.0 (Class 1)25.0 (Class 2)40+ (Blast Hazard)
BS EN 61482-1-1 Garment Rating & Shock Boundary
Mandatory Garment TierELIM ≥ 8 cal/cm²
Shock Boundary (BS EN 50110-1)300 mm Vicinity
PPE Tier & Boundary Justification:
Calculating boundary justification...
⚠WARNING
Arc Flash and Shock Hazard Appropriate Arc-Rated Clothing Required
Flash Boundary: 1.45 m
Incident Energy: 5.8 cal/cm²
Working Distance: 457 mm
Min Clothing: ELIM ≥ 8 cal/cm²
Shock Hazard: 400V •Vicinity Boundary: 300 mm •Standard: IEEE 1584 • BS EN 61482
Electrode Orientation & Enclosure DimensionsStandard Box (VCB · 32mm Gap · 457mm Distance)
Show Full Mathematical Derivation (AM2 Working Standard)
Standard ClauseFormulaSubstitutionResult
IEEE 1584 §6.2I_arc = I_bf × k_arc--
IEEE 1584 §6.3C_f = Orientation Factor--
IEEE 1584 §6.4E = (4.8 · (I_arc/20)^1.05 · t/0.1 · C_f · G/32) / (D/457)^x--
IEEE 1584 §6.5AFB = D × (E / 1.2)^(1/x)--
BS EN 61482-1-1ELIM ≥ E (Open Arc Rating)--
Blast Pressure Wave Hazard (> 40 cal/cm²): Above 40 cal/cm², arc flash events generate blast pressure shockwaves exceeding 2000 lbs/ft², vaporising copper (which expands 67,000 times) and projecting molten shrapnel. Thermal clothing cannot prevent concussive chest trauma. Remote racking devices or complete upstream safe isolation are strictly required under HSE HSG85.
Statutory Standards: IEEE 1584-2018 • BS EN 61482-1-1:2019 • BS EN 61482-1-2:2014 • BS EN 50110-1:2023 • EAWR 1989 Reg 14 • HSE HSG85