11kV Transformer IDMT Protection Curve & Discrimination Sizer
Prevent catastrophic upstream DNO 11kV feeder tripping during downstream LV faults. This tool evaluates IEC 60255 inverse definite minimum time (IDMT) curves, computes operating times across fault ranges, and evaluates the engineering guideline Δt ≥ 0.35s grading margin (NPAG / BS EN 60255-151) between 11kV relays and 400V air circuit breakers.
Regulation reference: BS EN 60255-151:2009 specifies overcurrent relay functional standards. BS 7671 Section 536 requires that protective devices be coordinated so that a fault is isolated by the device immediately upstream of the fault without causing uncoordinated tripping of upstream supplies.
Frequently Asked Questions
Why is a 0.35s (350 ms) discrimination margin required between 11kV and 400V?
The 350 ms grading margin specified in NPAG Chapter 9 accounts for physical real-world tolerances across both protection systems: circuit breaker opening and arc extinguishing time (80 ms), relay overshoot time (50 ms), CT saturation and ratio errors (100 ms), and a safety allowance (120 ms). If the margin falls below 350 ms, an LV busbar fault risks causing sympathetic tripping of the upstream 11kV DNO feeder circuit breaker.
Which IEC 60255 curve should be selected for transformer protection?
The Standard Inverse (SI) curve is standard for general distribution networks. However, for transformer incomers subject to high energisation inrush, the Extremely Inverse (EI) curve is strongly recommended. Its steep I²t slope tracks transformer withstand and facilitates discrimination with downstream BS 88 high-rupturing-capacity (HRC) fuses.