BS 7671 Conduit & Trunking Space Factor Sizer
Calibrated digital containment sizing instrument for BS 7671:2018+A4:2026. Calculates minimum steel or plastic conduit diameter and metallic trunking dimensions using the standard unit factor method from IET On-Site Guide Appendix E and the mandatory 45% trunking space factor.
Explore Interactive Visual Labs
Worked Example & Practical Reference (IET On-Site Guide)
Example Scenario: Sizing containment for six 2.5 mm² single-core 70°C PVC cables drawn through a 3.0 metre straight run of metal conduit connecting a local distribution board to machine isolators.
- Step 1 · Cable Factor Method: Because the conduit run is straight (0 bends) and does not exceed 3.0 metres in length, IET On-Site Guide Table E1 applies.
- Step 2 · Cable Factor Sum: From Table E1, each 2.5 mm² Class 2 stranded conductor has a factor of 43. Total cable factor ΣF = 6 × 43 = 258.
- Step 3 · Conduit Factor Evaluation: From Table E2, a 20 mm conduit has a capacity factor of 460, and 25 mm conduit has a factor of 800.
- Step 4 · Space Factor Fill: Fill percentage = (258 ÷ 460) × 100 = 56.1%. Since 258 ≤ 460, 20 mm conduit is compliant and selected.
- Step 5 · Grouping Verification: Under BS 7671 Table 4C1, six loaded conductors bunched together in conduit require an appropriate grouping derating factor ($C_g \approx 0.57$) to be applied to cable current-carrying capacity.
Frequently Asked Questions: Conduit & Trunking Capacity
What is the difference between Table E1 and Table E3 conduit cable factors?
Table E1 applies strictly to short, straight conduit runs not exceeding 3.0 metres in length with zero bends. Because pulling tension is low, cables can be packed more tightly without snagging. Table E3 applies to any run containing one or more bends, or straight runs exceeding 3.0 metres, and uses lower cable factor multipliers to prevent insulation damage during installation.
Why is trunking space factor capped at 45% instead of 100%?
Cables are circular and cannot physically pack into rectangular containment without air gaps. Furthermore, loaded conductors generate thermal heat. The 45% space factor in BS 7671 Appendix 5 guarantees adequate airspace for natural air convection and ensures cables can be drawn in and future additions made without crushing existing circuits.
Does passing containment space factor mean the cables are safe to carry current?
No. Space factor compliance only verifies physical drawing ease and avoids insulation damage under BS 7671 Regulation 522.8. Current-carrying capacity must be checked separately by applying BS 7671 Table 4C1 grouping derating factors ($C_g$), ambient temperature factors ($C_a$), and thermal insulation factors ($C_i$).
Regulation Reference: BS 7671:2018+A4:2026 Regulation 522.8 (Avoidance of damage during installation), Appendix 5 (Cable trunking and conduit space factor design rules), and IET On-Site Guide Appendix E (Tables E1 to E6).