DOL Motor Starter, Contactor & Overload Sizer

Precision digital instrument for three-phase Direct-On-Line (DOL) motor starters,AC-3 / AC-3e contactor selection, Class 10/20 thermal overload dial settings,BS 88-2 Type 2 coordination back-up fusing, BS 7671 feeder cable voltage dip, and BS EN 61439-2 Form 4 MCC panel segregation.

Plant-Room Ready: This switchgear sizing tool operates 100% offline in motor control centers and factory plant rooms.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Motor Rating & Feeder Parameters

Starter Engineering Telemetry

Standard Basis: BS EN IEC 60947-4-1:2019 • BS 88-2Coordination: Type 2 Certified
Recommended AC-3 / AC-3e ContactorFrame 18A · LC1D18
18A AC-3e
Overload Dial: 14.8 A (Class 10) • Thermal Headroom: +21.6%
Why not the next size down (12A contactor) or Type C MCB?12A contactor provides insufficient continuous thermal margin (-18.9% deficit vs 15% reserve) and risks contact welding under IE3 starting inrush. Standard Type C breakers trip instantaneously on the 115.4A inrush (peak 277A); Type D or BS 88 gM fuse is mandatory.
Starting Transient Voltage Dip
4.2% DipPASS · ≤ 8% Normal
0%≤ 8% Normal15% Warning> 15% Severe Dip
Motor Full Load Current (FLC):14.8 A
Locked-Rotor Starting Inrush:115.4 A (7.8×)
Peak Asymmetric Making Current:277 A (Inst. Peak)
Type 2 Back-up Fuse (BS 88-2 gM):32M40 (32A Body)
Alternative SCPD (Type D):20A Type D MCB / MPCB
Feeder Cable (BS 7671 SWA/XLPE):2.5 mm² (Iz = 31A)
Control Transformer VA (BS EN 60204-1):50 VA
Form 4 Segregation Level:Form 4b Type 6 (Individual Chambers)
Site Conditions & Switchgear OptionsStandard: IE3 Premium · Class 10 · 24V DC PELV · Form 4b

Glass-Box AM2 Mathematical Derivation Pad

Step-by-step first principles engineering derivation • BS EN 60947-4-1 • BS EN 60034-1

MOTOR COORDINATION ENGINE
RefFormulaWorking SubstitutionCalculated Result
[1]Full Load Current (FLC / I_b)
I_FLC = P_mech / (√3 × V_line × η × cos φ)
7500 W / (√3 × 400V × 0.904 × 0.84)14.8 A
[2]Locked-Rotor Starting Inrush (I_start)
I_start = k_inrush × I_FLC
7.8 × 14.8 A115.4 A (7.8×)
[3]Peak Asymmetric Making Current (I_peak)
I_peak = 2.4 × I_start (DC offset)
2.4 × 115.4 A277 A Peak
[4]Contactor AC-3 / AC-3e Frame Selection
I_e(AC-3e) ≥ 1.15 × I_FLC (Reserve)
1.15 × 14.8 A = 17.0 A → Frame 18A18 A (LC1D18, +21.6% Headroom)
[5]Thermal Overload Dial Setting
I_dial = I_FLC (Motor Nameplate Current)
Set dial to 14.8 A (Class 10 trip)14.8 A (Range: 11.1A to 17.0A)
[6]Type 2 Back-up Fuse (BS 88-2 gM)
Dual-rated motor fuse ladder selection
Ladder match for 14.8 A continuous32M40 (32A thermal body)
[7]Starting Transient Voltage Dip
ΔV_start = √3 × I_start × L × (R cos φ_s + X sin φ_s)
√3 × 115.4 A × 25 m on 2.5 mm² SWA16.8 V (4.2% dip, Normal)

Standard DOL Power & Control Circuit Diagram (BS EN 60617 & BS EN 61439-2)

BS EN 60617 Standard Engineering Symbols • BS EN 61439-2 Physical Segregation Boundaries

FORM 4: BUSBAR CHAMBERFORM 4: FUNCTIONAL STARTER UNIT (Q1, F0, KM1, F1)FORM 4b: SEPARATE CABLE TERMINATION CHAMBER3-PHASE 400V POWER CIRCUITCONTROL CIRCUIT (BS EN 60204-1)L1L2L3Q1 Main Switch IsolatorF0 (BS 88 gM)KM1F1 Overload RelayU1V1W1M+24V / L110V / NE-Stop (S0)Stop (S1)Start (S2)KM1 (13-14)F1 (95-96)KM1