Back to Tools DirectoryEV Charging (Section 722) Guide

EV Charging & Open-PEN Earthing Sizer

Verify circuit capacity, voltage drop, and statutory earthing compliance for electric vehicle supply equipment (EVSE). Evaluates 100% continuous duty cable sizing (Regulation 722.311), broken supply PEN touch voltages (Regulation 722.411.4.1), earth rod physical resistance limits, RCD selection (Regulation 722.531.3.101), and mandatory surge protection (Section 443/534).

Statutory Reg 722.411.4.1 Open-PEN Warning:An upstream Type A or Type B 30 mA RCD cannot protect against a broken supply PEN conductor because line and neutral currents remain balanced. On PME (TN-C-S) supplies outdoors, protection requires an approved device that isolates all live conductors and the protective earth conductor, a dedicated TT earthing island, or an earth electrode conforming to 722.411.4.1(ii).
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. EVSE Load & Circuit Parameters
2. Installation Method & Load Management

EVSE Circuit Telemetry

Standard Basis: BS 7671:2018+A4:2026 Section 722Max Drop: 5.0% (11.5 V)
Recommended Conductor CSA6.0 mm² Copper
6.0 mm²
Capacity: 47.0 A • Design Current $I_b$: 32.2 A • Drop: 4.70 V (2.04%)
0 A32.2 A (68% Thermal Loading)47.0 A
Why Not 4.0 mm²?

4.0 mm² failed current-carrying capacity (tabulated 37 A < required 40 A protective device rating).

Section 722.411.4.1 Earthing VerdictMethod (iv) Mandated
Method (iv) Open-PEN Detection Device Mandated

Under Reg 722.411.4.1(ii), maintaining touch voltage ≤ 70 V requires an earth resistance of ≤ 1.75 Ω. A standard 1.2 m rod achieves ~71.6 Ω in 100 Ω·m soil (physically unviable).

Max Permissible Ra (≤ 70V)≤ 1.75 Ω
1.2m Earth Rod Resistance~71.6 Ω
Mandatory Statutory Protection
  • RCD Protection (Reg 722.531.3.101): Type A 30 mA RCD + 6 mA DC RDC-DD (BS IEC 62955) or Type B RCD. Type AC prohibited.
  • Surge Protection (Section 443/534): Type 2 SPD mandated for outdoor charging equipment.
  • Duty Factor (Reg 722.311): Sized for 100% continuous unmanaged load.
Site Conditions & Earthing ParametersStandard: PME Outdoor · 30°C · 1 Circuit · ρ=100 Ω·m
Earthing & Environment (Reg 722.411.4.1)
Thermal & Grouping Factors (BS 7671 App 4)

Glass-Box AM2 Mathematical Derivation (BS 7671 Section 722)

Step-by-step calculation trace derived from first principles. Demonstrates design current calculation, environmental deratings, voltage drop verification, and open-PEN touch voltage limits under broken neutral conditions.

ParameterStatutory FormulaNumerical SubstitutionResult & Unit
1. Design Current (Ib)Ib = P / (U0 · cos φ)7400 W / (230 V · 1.0)32.2 A
2. Breaker & DeratingIt ≥ In / (Ca · Cg · Ci)40 A / (1.00 · 1.00 · 1.00)It ≥ 40.0 A (C=1.00)
3. Conductor CapacityTable 4D5 / 4E4A Lookup6.0 mm² Method C (It = 47 A)47.0 A (Pass)
4. Circuit Voltage DropΔV = (mV/A/m · Ib · L) / 1000(7.3 · 32.2 · 20) / 10004.70 V (2.04%)
5. Open-PEN Earth LimitRa ≤ 70 V / I_unbalance70 V / 40 ARa ≤ 1.75 Ω
6. Dwight Earth Rod CheckR = (ρ/2πL)·(ln(8L/d) - 1)(100 / 2π·1.2)·(ln(9.6/0.016) - 1)~71.6 Ω (Unviable)
Sparks Switchboard
Quick: