Generator Sizing Calculator
Sizing an emergency generator based purely on steady-state running kilowatts leads to catastrophic voltage collapse. On sites with motor drives, the required alternator capacity is almost always governed by the largest motor starting inrush. This tool calculates both steady and transient demands under ISO 8528 and BS 7671 Section 551, identifying which constraint dictates the physical machine rating.
Statutory ISO 8528 Duty Class Rule: Emergency Standby Power (ESP, 1.0) is for utility outage backup only. Prime Running Power (PRP, 0.90) allows variable load with unlimited hours. Continuous Operating Power (COP, 0.70) is mandated for 24/7 unvarying baseload generation.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
Alternator Transient Response & Non-Linear Loads:This instrument evaluates steady and step-loading boundaries per ISO 8528. Real-world generator sizing also depends on alternator subtransient reactance (Xd"), step load application sequencing, and harmonic crest factors introduced by large UPS units or variable speed drives. Always obtain manufacturer generator transient data sheets for site installation sign-off.
Standards reference: ISO 8528-1:2018 (Duty ratings ESP, PRP, COP), ISO 8528-5:2018 (Transient starting performance), BS 7671:2018+A3:2024 Section 551.