Commercial Solar PV, Battery Storage & EV Sizer
Integrate onsite renewable generation and battery storage (BESS) to charge electric vehicle fleets without exceeding agreed network import or export capacities. This tool sizes the battery buffer, determines your statutory DNO connection pathway (G98 vs G99), and models ENA EREC G100 export limitation failsafe timing.
DNO Regulatory Gate: Systems with aggregate generation exceeding 16A per phase (3.68 kW 1-ph / 11.04 kW 3-ph) require formal G99 advance approval before commissioning. ENA G100 schemes must achieve failsafe curtailment within 5.0 seconds.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
DNO Fast-Track Note (ENA EREC G99 Section 6.2): If the combined capacity of solar and battery storage is restricted so that simultaneous export can never exceed the export limitation threshold, certain DNOs offer streamlined assessment under Fast-Track Form A1-2.
Statutory Standards: ENA EREC G98 Issue 1 • ENA EREC G99 Issue 1 Amd 9 • ENA EREC G100 Issue 2 • BS 7671:2018+A4:2026 Section 712 & 722