BS 7671 Harmonic Derating & Neutral Sizing Calculator
Under non-linear loads (LED drivers, IT server power supplies, variable speed drives), triplen harmonic currents (3rd, 9th, 15th) do not cancel out at the star point of a three-phase system. Instead, they sum additively in the neutral conductor. This tool calculates the required rating factor (Ch) and detects when cable sizing must shift from the phase to the neutral conductor in accordance with BS 7671:2018+A4:2026 Table 4A3.
Statutory Precision: When 3rd harmonic content exceeds 33%, BS 7671 Table 4A3 mandates that the cable cross-sectional area be selected on the basis of the neutral current rather than the line current.