Back to Tools DirectoryHarmonics in Industrial Distribution Guide

BS 7671 Harmonic Derating & Neutral Sizing Calculator

Under non-linear loads (LED drivers, IT server power supplies, variable speed drives), triplen harmonic currents (3rd, 9th, 15th) do not cancel out at the star point of a three-phase system. Instead, they sum additively in the neutral conductor. This tool calculates the required rating factor (Ch) and detects when cable sizing must shift from the phase to the neutral conductor in accordance with BS 7671:2018+A4:2026 Table 4A3.

Statutory Precision: When 3rd harmonic content exceeds 33%, BS 7671 Table 4A3 mandates that the cable cross-sectional area be selected on the basis of the neutral current rather than the line current.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Load Current & Harmonic Content
63.0 A
Continuous balanced line current of the 3-phase 4-wire submain.
25%
Typical: Commercial offices 20% to 30%; Data centres / SMPS 35% to 50%.
2. Cable Construction & Reference Method

Harmonic Sizing & Neutral Telemetry

Effective Governing Design Current (Ib')
73.3 A
Min Conductor: 10 mm²Governing: Phase Sized
Neutral Current (IN)47.3 A3 × 25% × 63A additive
Table 4A3 Factor (Ch)0.8615% < h3 ≤ 33%
Neutral / Line Ratio (IN / IL)75.0% (In < IL)
0% (Linear)100% (Bottleneck Handover 33%)150%+ Severe
Table 4A3 Governing Basis:At 25% triplen content, the phase conductors are derated by factor Ch = 0.86 (Ib' = 73.3 A). Neutral current (47.3 A) remains below line current; phase conductors govern cable sizing.
Ambient Temperature & Circuit Grouping FactorsStandard (30°C · 1 circuit · Ca = 1.00)
BS 7671 Table 4B1 ambient correction factor (Ca). Base is 30°C.
BS 7671 Table 4C1 grouping derating factor (Cg).

Glass-Box AM2 Derivation: First-Principles Harmonic Sizing Pad

Step-by-step mathematical derivation evaluating neutral current, Table 4A3 rating factors, and cable conductor selection.

Step 1: Triplen Neutral Summation
IN = 3 × IL × (h3% / 100)
3 × 63.0 A × (25% / 100) = 47.3 A
Step 2: Table 4A3 Rule & Factor
15% < h3 ≤ 33%: Ch = 0.86
Ib' = 63.0 A / 0.86 = 73.3 A
Step 3: Tabulated Capacity (It)
It ≥ Ib' / (Ca × Cg)
73.3 A / (1.00 × 1.00) = 73.3 A
Step 4: BS 7671 Conductor Selection
Selected Table 4E2A Method C
Selected 10 mm² Cu XLPE (80 A ≥ 73.3 A)