Back to Tools DirectoryIndustrial Motor Starting Guide

Motor Starting Inrush & Voltage Dip Sizer

When an induction motor starts from standstill, it draws a severe locked-rotor current (typically 6 to 8 times Full Load Current under DOL). This inrush causes immediate voltage dips across the feeder cable and upstream switchboard, potentially tripping contactors or causing motor stall. This tool computes terminal voltage drop and motor torque depression from first principles per BS EN 60034-1 and ENA P28.

Physics Law (T ∝ V²): Induction motor starting torque is proportional to the square of terminal voltage. A 15% voltage dip reduces available breakaway torque to just 72% of rated!
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Motor Output Power (Shaft kW)
Rated Mechanical Output (kW)15 kW
Rated shaft output from motor rating plate per BS EN 60034-1.
2. Starting Regime & Feeder Cable
Cable Run Length (metres)45 m
BASIS: BS EN 60034-1 §12 & ENA P28DOL (7.0×) · 400V 3Φ
Peak Starting Inrush Current (Istart)
--.-A
Terminal Dip: --.-% (ΔV: --.- V) · Terminal: --.- V
Running FLC--.- A
Starting Torque--%
Starting kVA--.- kVA
Feeder Starting Voltage Dip6.1% Dip (ENA P28 Warning)
0% (Ideal)3% (P28 Flicker)10% (Industrial Max)15%+ (Stall Risk)
Recommended Switchgear & Protection (BS EN 60947-4-1)
Overload Dial-- A
Backup Fuse-- A
Breaker CurveType D
Starting Dynamics & Torque Assessment:
Calculating boundary justification...
Motor Nameplate Efficiency & Inrush Multiplier AdjustmentsStandard: IE3 (91.5%) · 0.85 PF · DOL (7.0×)
Efficiency Class (BS EN 60034-30-1)
Show Full Mathematical Derivation (AM2 Working Standard)
ClauseFormulaSubstitutionResult
BS EN 60034-1 §8I_FLC = P / (√3·V·η·cosφ)--
BS EN 60034-1 §12I_start = I_FLC × k_mult--
BS 7671 Tab 4D4BΔV = (mV/A/m × I_start × L) / 1000--
ENA P28 Issue 2% ΔV = (ΔV / V) × 100%--
Physics T ∝ V²T_start = k_regime × 180% × (V_term/V)²--
BS 88-2 / Reg 552Fuse ≥ k_fuse × I_FLC--
Industrial Engineering Compliance Note:Worked example to BS EN 60034-1 and BS EN 60204-1. Sizing starting currents for marginal supplies or generator sets must be verified against actual manufacturer nameplate data before installation (EAWR 1989).