AFDD Arc Fault Physics: 3D Consumer Unit, Plasma Dynamics & DSP Detection Workbench
How does a 32-bit microcontroller inside a single-module AFDD distinguish between the benign brush sparking of an electric power drill and a lethal 14 A series arc inside a damaged socket terminal? Explore the real-time 3D electromechanics of an authentic UK 1-module AFDD+RCBO installed on a DIN rail inside a non-combustible metal consumer unit (BS 7671 Reg 421.1.201), with its bottom comb busbar fork, blue neutral tail, and cream Functional Earth (FE) lead. Simulate Mayr-Cassie plasma dynamics, zero-crossing flat spots, high-frequency RF burst envelopes, and statutory tripping verification to BS EN 62606 Table 2 and BS 7671:2018+A3:2024 Regulation 421.1.7.
AFDD 3D Switchgear, Plasma Dynamics and Inrush Workbench
230V AC Single-Phase • Metal Consumer Unit (TH35-7.5 Rail) • Mayr-Cassie Arc Model • 10-50 MHz RF EnvelopeTime-Domain Oscilloscope • Current Flat-Spots & Re-Ignition Spikes
Log-Log Disconnection Curve • Type B/C MCB Magnetic Coordination
Show Step-by-Step Arc Energy & Tripping Derivations (AM2 Portfolio Standard)BS EN 62606:2013+A1:2017 & BS 7671:2018+A3:2024
Cassie-Mayr Dynamic Arc Energy & Conductance
g(t + Δt) = g(t) + [ (g / τ) · ( (u · i) / P_0 - 1 ) ] · ΔtNear current zero-crossings (±5 A), arc plasma conductance collapses as convective cooling (P0 ≈ 35 W) exceeds electrical power input. At a time constant τ = 25 μs, plasma extinguishes and creates the characteristic 1.35 ms zero-crossing flat spot.
Pyrolysis Ignition Energy Threshold in Cable Insulation
Q_pyrolysis = ∫ P_arc(t) dt ≥ Q_critical (100 Joules for PVC / Timber)PVC insulation decomposes thermally at 280°C to 300°C, releasing combustible hydrocarbons. Heating 0.1 g of PVC from ambient (20°C) to ignition temperature requires approximately 28 J. An un-cleared 338 W arc delivers 100 J in just 295 milliseconds.
Ring Final Circuit Mathematical Clamping & Glowing Connection Hazard
V_gap = I_leg · R_alt ≤ 13 A × 0.44 Ω = 5.72 V (< 12 V Minimum Arc Voltage)On a 32A ring final circuit, a series conductor break is bypassed by the alternate return leg. Because copper in air requires a minimum arc cathode-anode fall of ≥ 12 V to sustain plasma, the arc self-quenches, producing a resistive glowing connection.
Let-Through Energy (I²t) Coordination: AFDD vs Type B MCB
I²t = ∫ i²(t) dt • Fault current at 14 A RMSA standard 16A Type B MCB requires 3x to 5x In (48A to 80A) to trip magnetically. At 14A, the thermal bimetal takes over 120 seconds to trip, releasing over 40,000 Joules into the building fabric.
AFDD Plant-Room & AM2 Fault Diagnostic Engine
10 real-world breakdown scenarios. Practice safe isolation, live/dead testing interlocks, and statutory EAWR Reg 14 justification.
Select Diagnostic Scenario
Select a fault scenario to load site breakdown report.
Use the GS38 multimeter below to diagnose circuit integrity.
Approved Voltage Detector & MFT
Apprentice Test Logbook
| Time | Mode | Test Terminals | Reading | Status |
|---|---|---|---|---|
| No measurements recorded. Select function dial, position probes, and press "Take Measurement". | ||||
Electrical Inspection & Maintenance Bench Jobs
Step-by-step statutory test protocols and site fault finding routines for AFDD circuits.
Safe Isolation Protocol (BS 7671 Reg 641.1 / EAWR 1989 Reg 12 & 13)
Before opening the consumer unit visor, removing the dead-front escutcheon, or touching any AFDD terminal screw, strict safe isolation must be proven dead using an approved voltage indicator conforming to HSE Guidance Note GS38.
Statutory Legal Duty
Electricity at Work Regulations 1989 Regulation 12 mandates adequate means for cutting off electricity, while Regulation 13 mandates that adequate precautions shall be taken to prevent electrical equipment from becoming charged while work is carried out.
Statutory Law & Harmonised British Standards
Mandatory Final Circuits: HRRBs, HMOs, PBSA & Care Homes
Mandates AFDD installation conforming to BS EN 62606 on AC final circuits supplying socket-outlets with rated current not exceeding 32A in Higher-Risk Residential Buildings (≥18m or ≥7 storeys), HMOs, purpose-built student accommodation, and care homes.
Series & Parallel Arc Fault Detection Algorithms
Specifies dual-signature detection criteria. The DSP microcontroller evaluates the Cassie-Mayr 1.35ms zero-crossing current flat spot combined with 10 to 50 MHz broadband RF spectral energy, distinguishing lethal arc signatures from benign motor brush sparking.
Maximum Permissible Tripping Times & Let-Through Energy
Mandates disconnection within 1.00s at 2.5A, 0.50s at 5A, 0.25s at 10A, 0.15s at 16A, and 0.12s at 32A/63A. Guarantees arc let-through energy remains well below the 100 Joules pyrolysis ignition threshold for PVC cable insulation.
Non-Combustible Enclosures & Statutory Fire Containment
Within domestic premises, consumer units and switchgear assemblies must have non-combustible steel enclosures with tight seals, containing internal arc plasma and high-resistance terminal thermal runaway under statutory EAWR 1989 Regulation 4(1).
AFDD Apprentice CPD Verification Quiz (12 Questions)
Validate your understanding against British and International electrotechnical standards.
Scenario: During initial verification of a domestic ring final circuit, an insulation resistance tester applies 500V DC between conductors and records greater than 500 M ohms.