AFDD Arc Fault Physics: 3D Consumer Unit, Plasma Dynamics & DSP Detection Workbench

How does a 32-bit microcontroller inside a single-module AFDD distinguish between the benign brush sparking of an electric power drill and a lethal 14 A series arc inside a damaged socket terminal? Explore the real-time 3D electromechanics of an authentic UK 1-module AFDD+RCBO installed on a DIN rail inside a non-combustible metal consumer unit (BS 7671 Reg 421.1.201), with its bottom comb busbar fork, blue neutral tail, and cream Functional Earth (FE) lead. Simulate Mayr-Cassie plasma dynamics, zero-crossing flat spots, high-frequency RF burst envelopes, and statutory tripping verification to BS EN 62606 Table 2 and BS 7671:2018+A3:2024 Regulation 421.1.7.

Switchgear & Protection12 Min Interactive
• BS EN 62606:2013+A1:2017

AFDD 3D Switchgear, Plasma Dynamics and Inrush Workbench

230V AC Single-Phase • Metal Consumer Unit (TH35-7.5 Rail) • Mayr-Cassie Arc Model • 10-50 MHz RF Envelope
SLOW MOTION (15 RPM / 200x)ELECTRICAL: 50 Hz REAL TIME60 FPS● MONITORING (NORMAL)
3D View Mode:
Inspect Gear:
Visibility:
Left-Drag: Orbit • Right-Drag: Pan • Scroll: Zoom • Tap Part: Inspect
ISO 7200 WORKING DRAWING // BS EN 60617Single-Phase AFDD Final Circuit • Annex L Sequential Wire Numbering
METAL CONSUMER UNIT CHASSIS (BS 7671 REG 421.1.201) 230V AC SUPPLY L (Brown) N (Blue) Q0 100A COMB BUSBAR BRASS NEUTRAL BAR (BAR_N) BRASS EARTH BAR (BAR_E) Q1: AFDD + RCBO 32A TYPE B (BS EN 62606) L_IN (Comb) BLUE N-TAIL FE LEAD (Cream) SHUNT 30mA RCD HF TOROID 32-BIT DSP CORE CASSIE-MAYR / 8-CYC SOLENOID DE-ION L_OUT N_OUT 20A RADIAL SOCKET CIRCUIT (BS 7671 §433.1) SOCKET 1 Kettle (13A) SOCKET 2 Drill / Vacuum EOL
Load Current:10.0 A rms
Arc Plasma Physics:293 K • 0.0 V
Zero Flat Spot:0.00 ms (0.0%)
HF Noise (10-50MHz):-62.0 dBm (Benign)
DSP Accumulator:0 / 8 cycles
AFDD Trip Verdict:NO TRIP (PASS)
SWITCHGEAR OPERATOR STATION // BS EN 626061-Module DIN 43880 Fascia • Mechanical Latch
Monitoring (Circuit Healthy)
DOLLY (Q1)
TEST (T)
RESET LATCH
HEALTHY
SERIES ARC
PARALLEL
BENCH SIMULATION LEVERSTeaching & Network Fault Levers • Not Part of Switchgear
CASSIE-MAYR DYNAMIC ARC MODEL

Time-Domain Oscilloscope • Current Flat-Spots & Re-Ignition Spikes

Voltage (230V RMS) Circuit Current Zero Flat-Spot
Load Current: 10.0 A rmsFlat-Spot: 0.00 msGap Voltage: 0.0 VStatus: HEALTHY LINEAR
BS EN 62606 TABLE 2 & MCB COORDINATION

Log-Log Disconnection Curve • Type B/C MCB Magnetic Coordination

AFDD Limit (Table 2) Type B MCB (3-5x) Type C MCB (5-10x) Operating Locus
HF Noise: -62.0 dBmStatutory Max Time: 0.25 sDSP Cycles: 0 / 8Trip Verdict: PASS (NO TRIP)
Show Step-by-Step Arc Energy & Tripping Derivations (AM2 Portfolio Standard)
BS EN 62606:2013+A1:2017 & BS 7671:2018+A3:2024
Step-by-step engineering workingTransparent first-principles maths
STEP 1

Cassie-Mayr Dynamic Arc Energy & Conductance

g(t + Δt) = g(t) + [ (g / τ) · ( (u · i) / P_0 - 1 ) ] · Δt

Near current zero-crossings (±5 A), arc plasma conductance collapses as convective cooling (P0 ≈ 35 W) exceeds electrical power input. At a time constant τ = 25 μs, plasma extinguishes and creates the characteristic 1.35 ms zero-crossing flat spot.

Substitution (14 A series arc):u = 24.0 V • i = 14.1 A • P_in = 338.4 W • P_0 = 35 W
Instantaneous Arc Power:P_arc = 338.4 W (Continuous local heating)
STEP 2

Pyrolysis Ignition Energy Threshold in Cable Insulation

Q_pyrolysis = ∫ P_arc(t) dt ≥ Q_critical (100 Joules for PVC / Timber)

PVC insulation decomposes thermally at 280°C to 300°C, releasing combustible hydrocarbons. Heating 0.1 g of PVC from ambient (20°C) to ignition temperature requires approximately 28 J. An un-cleared 338 W arc delivers 100 J in just 295 milliseconds.

AFDD Disconnection Time (BS EN 62606 Table 2 at 14 A):t_break ≤ 0.150 s (7.5 cycles at 50 Hz)
Maximum Let-Through Energy:E_let_through = 338.4 W × 0.150 s = 50.8 Joules (< 100 J threshold)
STEP 3

Ring Final Circuit Mathematical Clamping & Glowing Connection Hazard

V_gap = I_leg · R_alt ≤ 13 A × 0.44 Ω = 5.72 V (< 12 V Minimum Arc Voltage)

On a 32A ring final circuit, a series conductor break is bypassed by the alternate return leg. Because copper in air requires a minimum arc cathode-anode fall of ≥ 12 V to sustain plasma, the arc self-quenches, producing a resistive glowing connection.

Statutory Limitation:AFDD DSP detects zero RF hiss and zero flat spot because no arc plasma exists.
Inspection Remedy:End-to-end resistance test (r1, rn, r2 per BS 7671 §643.2.1) + Thermal Imaging
STEP 4

Let-Through Energy (I²t) Coordination: AFDD vs Type B MCB

I²t = ∫ i²(t) dt • Fault current at 14 A RMS

A standard 16A Type B MCB requires 3x to 5x In (48A to 80A) to trip magnetically. At 14A, the thermal bimetal takes over 120 seconds to trip, releasing over 40,000 Joules into the building fabric.

AFDD Energy Reduction Factor:(40,600 J) / (50.8 J) = 800x Thermal Energy Reduction
Statutory Protection Verdict:BS 7671 Reg 421.1.7 compliance verified • Fire risk eliminated
Formula & factors cross-checked against BS EN 62606:2013+A1:2017 & BS 7671:2018+A3:2024. Free of black-box approximations.
NET AM2 WORKSHOP SIMULATOR // HSE GS38

AFDD Plant-Room & AM2 Fault Diagnostic Engine

10 real-world breakdown scenarios. Practice safe isolation, live/dead testing interlocks, and statutory EAWR Reg 14 justification.

FAULT SCENARIO: NONE (HEALTHY)
BREAKDOWN REPORT

Select Diagnostic Scenario

Observed Symptom:

Select a fault scenario to load site breakdown report.

Apprentice Test Hint:

Use the GS38 multimeter below to diagnose circuit integrity.

Syllabus Reference:NET AM2 • C&G 2365 Unit 305
HSE GS38 INSTRUMENT

Approved Voltage Detector & MFT

GS38 Verified • CAT IV 600V
PROVED: NOLIVE: 0VHOLD
---.-V AC
Select dial mode and probe test terminals
ROTARY FUNCTION SELECTOR:
DIAGNOSTIC EVIDENCE

Apprentice Test Logbook

TimeModeTest TerminalsReadingStatus
No measurements recorded. Select function dial, position probes, and press "Take Measurement".
PRACTICAL WORKBENCH PROCEDURES

Electrical Inspection & Maintenance Bench Jobs

Step-by-step statutory test protocols and site fault finding routines for AFDD circuits.

Safe Isolation Protocol (BS 7671 Reg 641.1 / EAWR 1989 Reg 12 & 13)

Before opening the consumer unit visor, removing the dead-front escutcheon, or touching any AFDD terminal screw, strict safe isolation must be proven dead using an approved voltage indicator conforming to HSE Guidance Note GS38.

Step 1: Identify consumer unit main switch-disconnector Q0 and obtain customer permission to isolate.
Step 2: Rotate Q0 handle to OFF (0). Fit safety lockout hasp, padlock, and warning tag. Retain the key in your personal custody.
Step 3: Test GS38 two-pole voltage indicator on dedicated proving unit to confirm operational status.
Step 4: Prove dead on all outgoing ways: Line to Neutral, Line to Earth, Neutral to Earth, and busbar comb prongs.
Step 5: Re-test voltage indicator on proving unit to verify probe and fuse integrity.

Statutory Legal Duty

Electricity at Work Regulations 1989 Regulation 12 mandates adequate means for cutting off electricity, while Regulation 13 mandates that adequate precautions shall be taken to prevent electrical equipment from becoming charged while work is carried out.

Statutory Law & Harmonised British Standards

STATUTORY & CONSENSUS STANDARDS
BS 7671:2018+A3:2024 Reg 421.1.7

Mandatory Final Circuits: HRRBs, HMOs, PBSA & Care Homes

Mandates AFDD installation conforming to BS EN 62606 on AC final circuits supplying socket-outlets with rated current not exceeding 32A in Higher-Risk Residential Buildings (≥18m or ≥7 storeys), HMOs, purpose-built student accommodation, and care homes.

BS EN 62606:2013+A1:2017 §5.3

Series & Parallel Arc Fault Detection Algorithms

Specifies dual-signature detection criteria. The DSP microcontroller evaluates the Cassie-Mayr 1.35ms zero-crossing current flat spot combined with 10 to 50 MHz broadband RF spectral energy, distinguishing lethal arc signatures from benign motor brush sparking.

BS EN 62606 Table 2

Maximum Permissible Tripping Times & Let-Through Energy

Mandates disconnection within 1.00s at 2.5A, 0.50s at 5A, 0.25s at 10A, 0.15s at 16A, and 0.12s at 32A/63A. Guarantees arc let-through energy remains well below the 100 Joules pyrolysis ignition threshold for PVC cable insulation.

BS 7671 Reg 421.1.201 & EAWR 1989

Non-Combustible Enclosures & Statutory Fire Containment

Within domestic premises, consumer units and switchgear assemblies must have non-combustible steel enclosures with tight seals, containing internal arc plasma and high-resistance terminal thermal runaway under statutory EAWR 1989 Regulation 4(1).

TECHNICAL ASSESSMENT

AFDD Apprentice CPD Verification Quiz (12 Questions)

Validate your understanding against British and International electrotechnical standards.

Question 1 of 12• Score 0 / 12
BS 7671 Chapter 64 / C&G 2365 Unit 305

Scenario: During initial verification of a domestic ring final circuit, an insulation resistance tester applies 500V DC between conductors and records greater than 500 M ohms.

Why does this test fail to detect a damaged, partially severed conductor terminal that subsequently arcs under load?

Sparks Switchboard