Machinery Functional Safety Performance Level (PL) Sizer

Under the UK Supply of Machinery Regulations and PUWER 98 Regulation 19, safety-related control circuits (emergency stops, interlocks, light curtains) must achieve a Performance Level matching the assessed hazard risk. This tool evaluates Required Performance Level (PLr) via the ISO 13849-1 risk graph and calculates Achieved PL from system Category, MTTFd, and Diagnostic Coverage.

Designated Safety Standard Gate: A safety function satisfies BS EN ISO 13849-1 when Achieved PL ≥ Required PLr and Common Cause Failure (CCF) scoring achieves ≥ 65 points for redundant architectures.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Risk Graph Hazard Assessment (Determines PLr)
2. Control System Designated Architecture
Hazard: S2 / F2 / P2Architecture: Category 4
BASIS: BS EN ISO 13849-1 & IEC 62061PL e / SIL 3
Achieved Performance Level (PL)
PL eAchieved
Required Target: PL e (Risk Graph S2/F2/P2)
IEC 62061 SILSIL 3
PFHd Probability≥ 10⁻⁸ to < 10⁻⁷
CCF GatePASS (85 pts)
ISO 13849-1 Performance Level ProgressionPL e Compliant
PL a
PL b
PL c
PL d
PL e
Designated Architecture Verification
Category 4 (High MTTFd, High DC, CCF 85 pts). Dual-channel redundancy with continuous pulsed testing.
Why Architecture Category Matters:
Why not Category 3? Category 3 achieves PL e only with High MTTFd and Medium/High DC. Any accumulation of undetected faults breaches Cat 3 integrity in extreme hazard applications.
Site Conditions & Component ReliabilityStandard Architecture (High MTTFd · High DC · CCF 85 pts)
Show Full Mathematical Derivation (AM2 & Machinery Safety Standard)
BS EN ISO 13849-1:2023
Step-by-step engineering workingTransparent first-principles maths
Step 1 · Risk Graph Hazard Evaluation

Required Performance Level (PLr)

PLr = f(Severity, Frequency, Possibility)
S2 (Severe) × F2 (Frequent) × P2 (Scarcely Possible) → PL e
BS EN ISO 13849-1:2023 Clause 4.5 · Annex A Risk Graph
Step 2 · Designated Architecture Category

Control System Architecture Selection

Category = Physical Topology & Fault Tolerance
Category 4: Dual-channel redundancy with dynamic diagnostic testing
BS EN ISO 13849-1:2023 Clause 6.2 · Designated Architectures
Step 3 · Achieved Performance Level Evaluation

Achieved Performance Level (PL)

PL = Table 5 Matrix (Category, MTTFd, DCavg)
Category 4 + High MTTFd + High DC → PL e
BS EN ISO 13849-1:2023 Clause 4.5.4 · Table 5 Evaluation Matrix
Step 4 · Common Cause Failure Evaluation

Common Cause Failure (CCF) Scoring Gate

Score ≥ 65 Points (Mandatory for Cat 2, 3, 4)
Assessed score: 85 points → COMPLIANT
BS EN ISO 13849-1:2023 Annex F Scoring Matrix
Step 5 · IEC 62061 SIL & PFHd Mapping

Probability of Dangerous Failure per Hour

PFHd Claim Limit Mapping
Achieved PL e maps to SIL 3 → ≥ 10⁻⁸ to < 10⁻⁷ /h
BS EN IEC 62061:2021 · ISO 13849-1 Table 3 Relationship
Step 6 · Statutory Compliance Sign-Off

Overall Safety Function Compliance

Achieved PL ≥ PLr AND CCF ≥ 65
Achieved PL e ≥ Required PL e · CCF 85 ≥ 65 → PASS
UK Supply of Machinery Regulations 2008 · PUWER 1998 Reg 19
Worked Example & Engineering Rationale: Robotic Packaging Cell

Design Scenario: An automated packaging cell features a high-speed robotic palletiser. The risk assessment identifies:

  • Severity (S2): Severe crushing hazard resulting in fatality or irreversible disability.
  • Frequency (F2): Frequent operator access required (loading film roll multiple times per shift).
  • Possibility (P2): High-speed robot envelope with scarcely possible evasive reaction time.
  • Risk Graph Result: S2 + F2 + P2 → Required PLr e (Highest performance level required).
  • Hardware Design Verification: The engineer specifies a Category 4 safety circuit with dual force-guided safety relays, redundant feedback monitoring contacts (High DC ≥ 99%), and premium safety contactors (MTTFd High). CCF score evaluates to 85 points.
  • Verdict: Achieved PL is PL e. Since Achieved PL (e) ≥ PLr (e) and CCF ≥ 65, the design satisfies BS EN ISO 13849-1:2023 and the UK Supply of Machinery Regulations.
Formula & factors cross-checked against BS EN ISO 13849-1:2023. Free of black-box approximations.
CE / UKCA Marking & Technical File Mandate:For machinery placed on the UK or EU market, documentation proving the achieved PL (including component B10d data, failure rates, and validation test sheets per ISO 13849-2) must be preserved in the machine statutory technical file for a minimum of 10 years.

Designated Standards: BS EN ISO 13849-1:2023 • BS EN ISO 13849-2:2012 • BS EN IEC 62061:2021 • PUWER 1998 Regulation 19