Regulatory Status and Context
BS 7671:2018+A1:2020 was published in February 2020 as an urgent standalone amendment. It was released free of charge by the IET and BSI to accelerate the safe rollout of electric vehicle charging infrastructure across Great Britain and Northern Ireland.
BS 7671 is a non-statutory national standard that derives legal backing from citations in statutory instruments, including the Electricity at Work Regulations 1989 (via HSE Memorandum HSR25) and Part P of the Building Regulations. Under BS 7671 non-retrospection rules, existing installations that complied with earlier standards at construction are not automatically defective, though duty holders remain under continuous duties under EAWR 1989 Regulation 4(1) (construction) and Regulation 4(2) (maintenance) to prevent danger, so far as is reasonably practicable.
The amendment was subsequently incorporated into BS 7671:2018+A2:2022 (The Brown Book) and continues in full technical effect as part of the current edition, BS 7671:2018+A4:2026 (The Orange Book).
What Changed: Section 722 and PME Earthing
The primary driver for Amendment 1 was the physical danger of an open-PEN fault on a Protective Multiple Earthing (TN-C-S / PME) supply when charging an electric vehicle outdoors.
If the combined protective and neutral conductor (PEN) fractures upstream on the distribution network, the vehicle body (connected to the installation protective conductor via the charging lead) can rise towards phase potential. A person standing on true earth outdoors while touching the car body would receive a severe or fatal electric shock.
The Overhaul of Regulation 722.411.4.1
Before Amendment 1, connecting an EV charger to a PME supply required either an independent earth electrode or proof that an earth electrode was not reasonably practicable. In practice, contractors routinely drove copper earth rods without verifying whether the resistance was low enough to protect against open-PEN touch voltages.
Amendment 1 replaced this ambiguity with five precise compliance paths under Regulation 722.411.4.1 for outdoor EV charging points connected to a PME supply:
- Indent (i) Earth Electrode Sizing: The charging point is connected to an earth electrode whose resistance to earth $R_A$ is sufficiently low that touch voltage under an open supply PEN conductor cannot exceed 70V rms. In practice, domestic network impedances require resistances below 1 ohm, which is rarely achievable on suburban sites.
- Indent (ii) Touch Voltage Device: Protection by a device that continuously monitors touch voltage against true earth and disconnects all live conductors and the protective conductor within 5.0 seconds if touch voltage exceeds 70V rms.
- Indent (iii) Line-to-Neutral Voltage Monitor: Protection by an electronic device that continuously monitors supply voltage between line and neutral. If voltage exceeds 253V rms or drops below 207V rms, the device automatically isolates all live conductors and the protective earth conductor within 5.0 seconds as prescribed by BS 7671 Reg 722.411.4.1(iii) (with under 4.0 seconds typical of commercial manufacturer performance).
- Indent (iv) Three-Phase Neutral Displacement: On three-phase installations supplying solely three-phase loads, connection to a device that measures the neutral point displacement voltage against true earth.
- Indent (v) Equivalent Safety Alternative: Use of alternative proprietary equipment providing equivalent safety, certified by the manufacturer.
Practical Implications and Engineering Limitations
Indent (iii) revolutionised the UK EV charging industry. It enabled UK manufacturers to build internal electronic open-PEN detection circuits directly into home charging units, eliminating the need to install external earth rods on tarmac and concrete driveways.
However, electrical design engineers must recognise the fundamental limitation of Indent (iii) monitoring: because it does not measure potential relative to true earth, it relies on load imbalance to shift the line-to-neutral voltage. Under balanced three-phase vehicle charging loads where neutral current is minimal during an open PEN fault, the supply voltage can remain within the 207V to 253V band, leaving the vehicle chassis elevated at a hazardous touch voltage until an appliance in the property creates sufficient imbalance to trigger the unit.
On this site: see our guides on open-PEN fault detection and earthing, the EV charging cable sizer, and the maximum Zs calculator.
Timeline
Authoritative Sources
- IET Wiring Matters: Section 722 Electric Vehicle Charging Installations (A1:2020)
- IET BS 7671 Updates: Archive of Historic Amendments
- NICEIC: Electric Vehicle Charging Regulations & Guidance
This archive page reports what changed and when, with verified sources. It does not replace competent engineering judgement. Always work from the published standard and manufacturer technical datasheets.