Regulatory Status and Context

Amendment 3 to BS 7671:2018 was published on 31 July 2024 as a targeted, free-to-download PDF amendment by the IET and BSI. It addressed an immediate electrical safety issue arising from the rapid domestic adoption of solar photovoltaic arrays, home battery energy storage systems (BESS), and vehicle-to-grid (V2G) technology.

BS 7671 is a non-statutory standard given legal weight through references in secondary legislation, including the Electricity at Work Regulations 1989 (via HSE Guidance HSR25) and Part P of the Building Regulations. Under BS 7671 non-retrospection rules, existing installations that complied with earlier standards at construction are not automatically defective, though duty holders remain under continuous duties under EAWR 1989 Regulation 4(1) (construction) and Regulation 4(2) (maintenance) to prevent danger, so far as is reasonably practicable.

Following the standard six-month industry transition period concluding on 15 October 2026, Amendment 3 was withdrawn as a standalone standard. Its technical provisions were absorbed and expanded inside BS 7671:2018+A4:2026 (The Orange Book), specifically across Chapter 53 (Protection, Isolation, Switching, Control and Monitoring) and the dedicated stationary battery storage chapter.

What Changed: Bidirectional Protective Devices

Before Amendment 3, the Wiring Regulations assumed electrical current flowed in a single direction: from the distribution network operator (DNO) cut-out through the consumer unit to individual final circuit loads.

Domestic solar inverters and battery systems altered this assumption by turning consumer units into bidirectional nodes. Current can flow from the grid into the property, or from the storage inverter back towards the grid and other final circuits.

Regulation 530.3.201

Amendment 3 introduced Regulation 530.3.201, requiring that selection and erection of equipment account for any potential bidirectional power flows. Specifically:

  • Where a protective device is marked with directional terminals (such as “Line” and “Load”, or directional arrows), power must only flow in the indicated direction unless the manufacturer explicitly certifies bidirectional operation.
  • Miniature circuit breakers (MCBs), residual current circuit breakers (RCCBs), and residual current breakers with overcurrent protection (RCBOs) installed on inverter supplies must have manufacturer approval for reverse feed.
  • Certain electronic RCBOs incorporate internal electronics that rely on the line terminal for internal supply. Back-feeding such devices can result in failure of the electronic detection circuit or thermal damage to internal test components.

Practical Implications for Installers

When adding solar PV or stationary battery storage to existing consumer units, electrical contractors must verify the product documentation for all consumer unit devices:

  • Consumer Unit Busbars: Verify whether the busbar arrangement and incoming main switch can handle combined grid and inverter generation currents without exceeding busbar thermal ratings (Regulations 134.1.1, 510.3, and Chapter 55).
  • RCBO Suitability: Confirm with the manufacturer that the specific RCBO model is bidirectional. Many major UK manufacturers updated product lines to explicitly state bidirectional compatibility.
  • Sub-Consumer Units: While many modern consumer units are certified for bidirectional generation within specified ratings, installing a separate generation board directly after the meter tails remains standard practice where existing domestic assemblies contain unidirectional devices or lack busbar capacity.

On this site: see our guides on battery storage, EPS and islanding, G98 and G99 notifications, and the maximum demand diversity sizer.

Timeline

31 Jul 2024Amendment 3:2024 published as a free PDF amendment by IET and BSI
15 Apr 2026Amendment 4:2026 published, absorbing Amendment 3 provisions
15 Oct 2026Consolidation: Carried forward as active requirement in BS 7671:2018+A4:2026

Authoritative Sources

This archive page reports what changed and when, with verified sources. It does not replace competent engineering judgement. Always work from the published standard and manufacturer technical datasheets.